Controllogix Example: Eds Add-On Profile (Aop) Generic I/O Messaging - Mitsubishi 700 Series Instruction Manual

Plug-in option. ethernet multiprotocol communication interface
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

Confirm the setting of the "Requested Packet Interval (RPI)". The RPI defines the amount of time (in
milliseconds) between data exchanges across an I/O connection. The smallest RPI supported by the
interface card is 1ms. Click "OK" when done.
14) You should now see the interface card in the 1756-ENBT/A branch under the I/O Configuration in
the controller organizer view. The full I/O Configuration tree should appear similar to Figure 37.
15) Continue with the AOP Generic I/O Messaging example in section 9.2.11.1 or AOP AC/DC Drive
Profile example in section 9.2.11.2.

9.2.11.1 ControlLogix Example: EDS Add-On Profile (AOP) Generic I/O Messaging

This section will demonstrate how to configure the EtherNet/IP Generic I/O connection.
1) Complete all steps in section 9.2.11.
2) Locate the interface card in the 1756-ENBT/A branch under the "I/O Configuration" in the controller
organizer view. Right click on the interface card, choose "Properties", and select the "General" tab.
Figure 37: AOP Interface Card I/O Configuration
PROTOCOL-SPECIFIC INFORMATION
9
135

Hide quick links: