Generic Process I/O Status And Control Object Settings - Mitsubishi 700 Series Instruction Manual

Plug-in option. ethernet multiprotocol communication interface
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

PROTOCOL-SPECIFIC INFORMATION
Application ID
The client will only process GOOSE messages with a matching application ID.
Destination Multicast Address
The GOOSE message will be sent to the specified destination multicast address.

9.10.4 Generic Process I/O Status and Control Object Settings

The Generic Status objects define the structure of "status" data, which are typically read-only registers.
The Generic Control objects will define the structure of the "command" data, which are writeable
registers. These objects allow the creation of custom-built GGIO process I/O. Up to 100 Generic Status
and 100 Generic Control objects can be created. Note that the inverter register value is a 16-bit integer,
so only the lower 16-bits of the object's 32-bit integer value is useful.
Name
The name of this object as discovered by the client. The name is automatically generated depending on
the instance.
Instance
The instance number of this object. It is recommend to start at 0.
258