1.2 Inverter and peripheral devices

Three-phase AC power supply
Use within the permissible power supply
specifications of the inverter.
(Refer to page 366)
Moulded case circuit
breaker (MCCB)
or earth leakage circuit
breaker (ELB), fuse
The breaker must be selected carefully since
an in-rush current flows in the inverter at
power ON.
(Refer to page 4)
Magnetic contactor(MC)
Install the magnetic contactor to ensure safety.
Do not use this magnetic contactor to start and
stop the inverter.
Doing so will cause the inverter life to be shorten.
(Refer to page 4)
Reactor (FR-HAL, FR-HEL)
Install reactors to suppress harmonics and to
improve the power factor. An AC reactor (FR-HAL)
(option) is required when installing the inverter near
a large power supply system (1000kVA or more).
The inverter may be damaged if you do not use
reactors.
Select the reactor according to the model.
For the 01160 or less, remove the jumpers across
terminals P/+ and P1 to connect to the DC reactor.
(Refer to page 4.)
AC reactor
(FR-HAL)
EMC filter
(ferrite core)
(FR-BLF)
The 01160 or less
has a built-in common
mode choke.
High power factor
converter
(FR-HC
, MT-HC
)
*1
*2
Power supply harmonics
can be greatly suppressed.
Install this as required.
*1 Compatible with the 01160 or less.
*2 Compatible with the 01800 or more.
: Install these options as required.
CAUTION
· Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side. This will
cause the inverter to trip or the capacitor, and surge suppressor to be damaged. If any of the above devices are connected,
immediately remove them.
· Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication
devices (such as AM radios) used near the inverter. In this case, set the EMC filter valid to minimize interference.
(Refer topage 13.)
· Refer to the Instruction Manual of each option and peripheral devices for details of peripheral devices.
Programmable
controller
POWER
MODE
RUN
ERR
USER
BAT
BOOT
PULL
USB
PULL
DC reactor
P/+
(FR-HEL)
For the 01800 or more, a
DC reactor is supplied.
Always install the reactor.
Brake unit
(FR-BU2, FR-BU
Power regeneration
common converter
Resistor unit
(FR-CV
)
*1
(FR-BR
*1
Power regeneration
converter (MT-RC
)
The regeneration braking
*2
capability of the inverter can be
Greater braking capability
is obtained.
exhibited fully.
Install this as required.
Install this as required.
Inverter and peripheral devices
Human machine
interface
Inverter
(FR-F700)
The life of the inverter is influenced by surrounding air
RUN
MNG
RUN
MNG
T.PASS
D.LINK
T.PASS
D.LINK
SD
RD
SD
RD
ERR
ERR
ERR
ERR
temperature. The surrounding air temperature should be
as low as possible within the permissible range.
Especially when mounting the inverter inside an
RS-485 terminal block
enclosure,
temperature. (Refer to page 9)
The inverter can be connected
Wrong wiring might lead to damage of the inverter. The
with a computer such as a
control signal lines must be kept fully away from the main
programmable controller and
circuit to protect them from noise.(Refer to page 12)
with GOT (human machine
Refer to page 13 for the built-in EMC filter.
interface).
It supports Mitsubishi inverter
protocol, Modbus-RTU (binary)
protocol and BACnet MS/TP
protocol.
R/L1 S/L2 T/L3
P1
P/+
N/-
U V W
Earth
, MT-BU5
)
*1
*2
P/+
PR
Devices connected to the output
P/+
Do not install a power factor correction capacitor,
PR
surge suppressor or EMC filter (capacitor) on the
output side of the inverter.
When installing a moulded case circuit breaker on the
output side of the inverter, contact each manufacturer
, MT-BR5
)
*2
for selection of the moulded case circuit breaker.
Earth
To prevent an electric shock, always earth the
motor and inverter.
take
cautions
of
the
surrounding
EMC filter
(ferrite core)
(FR-BSF01, FR-BLF)
Install an EMC filter (ferrite
core) to reduce the
electromagnetic noise
generated from the inverter.
Effective in the range from
about 0.5MHz to 5MHz.
A wire should be wound four
turns at a maximum.
Motor