Interface Description; Overview; X524 Electronics Power Supply - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

8.2.3

Interface description

8.2.3.1

Overview

Figure 8-20
8.2.3.2

X524 electronics power supply

Table 8- 22
X524 electronics power supply
Terminal
+
+
GND
GND
Type: Screw-type terminal 2 (Page 371)
Max. cross-section that can be connected: 2.5 mm²
The maximum cable length that can be connected is 30 m.
Note
The two "+" and/or "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Supplementary system components and encoder system integration
Connection for the solenoid of the motor brake
Connection for the 24 VDC power supply
Connection for the pre-fabricated (CTRL) to the Power Module, Blocksize format
Interface description: Safe Brake Relay
Function
Electronics power supply
Electronics power supply
Electronics ground
Electronics ground
8.2 Option module Safe Brake Relay
Technical data
Voltage: 24 V (20.4 ... 28.8 V)
Current consumption: max. 0.3 A (without motor
holding brake)
Maximum current via jumper in connector: 20 A
(15 A according to UL/CSA)