Siemens SINAMICS S120 Manual page 37

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Installation altitude
Operation with low overload
Operation with high overload
Mechanical environmental conditions
Long-term storage
Transport
Operation
Vibration test in operation
Shock test in operation
Product packaging (storage packaging) is individual packaging for storage - and does not satisfy the requirements for
1)
transport. As a consequence, product packaging is therefore not suitable for shipping.
Transport packaging is either packaging that is directly suitable for transport - or secondary packaging, which together
2)
with the product packaging, satisfies the requirements for transport.
Increased ruggedness regarding temperature range and relative humidity; therefore better than 3K3
3)
Observe the permissible temperatures for the Control Unit and possibly the operator panel (IOP or BOP-2).
4)
Table 2- 4
Certificates
Declarations of Conformity
FSA-FSC approvals
Approvals FSD-FSF
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
0 ... 1000 m above sea level without derating
0 ... 2000 m above sea level without derating
> 2000 ... 4000 m above sea level
Reduction of the ambient temperature by 3.5 K per 500 m
Operation on line supply systems with grounded neutral point, or
Operation on an isolating transformer with secondary grounded neutral point
Class 1M2 according to EN 60721-3-1, in product packaging
Class 2M3 according to EN 60721-3-2, in transport packaging
Class 3M1 according to EN 60721-3-3
According to IEC 60068-2-6 test Fc (sinusoidal)
10 ... 57 Hz: 0.075 mm deflection amplitude
57 ... 150 Hz: 1g acceleration amplitude
10 frequency cycles per axis
According to IEC 60068-2-27 test Ea (half-sine)
5 g peak acceleration
30 ms duration
3 shocks in all three axes in both directions
CE (Low Voltage, EMC and Machinery Directives)
cULus acc. to UL 508C/CSA 22.2 No. 274
RCM (C-Tick)
SEMI F47
KCC only with internal or external line filters for Category C2
RoHS
EAC
cULus acc. to UL 508C/CSA 22.2 No. 274
RCM (C-Tick)
SEMI F47
KCC only with internal or external line filters for Category C2
WEEE (Waste Electrical & Electronic Equipment)
RoHS
EAC
System overview
2.5 System data
1)
2)
37

Advertisement

Table of Contents
loading

Table of Contents