Motor-side power components
6.2 Chassis
NOTICE
Damage to the Power Module by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use sine-wave filters that SIEMENS has released for SINAMICS.
NOTICE
Risk of damaging sine-wave filter by exceeding the maximum output frequency
The maximum permissible output frequency when sine-wave filters are used is 150 Hz. The
sine-wave filter can be damaged if the output frequency is exceeded.
• When commissioning, you must always activate the sine-wave filter connected to the
NOTICE
Damage to the sine-wave filter if a motor is not connected
Sine-wave filters, which are operated without a motor being connected, can be damaged or
destroyed.
• Never operate a sine-wave filter connected to the Power Module without a connected
Note
Keep the connecting cables to the Power Module as short as possible (max. 5 m).
198
Power Module (see SINAMICS S120/S150 List Manual).
motor.
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5