Troubleshooting
Table 11-5
Operator control errors
Cl.
No.
Operator control errors
1 (01) 1 (01)
Software limit switch, beginning is passed
Cause
Effect
Elimina-
tion
1 (01) 2 (02)
Software limit switches, end is passed
Cause
Effect
Elimina-
tion
1 (01)
3 (03)
Beginning of traversing range passed
Cause
Effect
Elimina-
tion
1 (01) 4 (04)
Traversing range end passed
Cause
Effect
Elimina-
tion
Cl. = Detail event class, No. = Detail event number
Note: Value (xx) = Hexadecimal notation of the error number
11-14
Error message,
error analysis and elimination
Error response: "Everything Off", as in Table 11-2
Limit switch passed: in "Control" or "Correction" operating mode
The limit switch position is passed by the necessary stopping
distance.
Set actual value is not executed.
Following acknowledgment of the error, it is possible to tra-
verse to the working range.
Alter value of software limit switch (MD21)
Disable limit switch monitoring!
(With the limit switches (MD21/22) disabled, the travel range
limits are established by the maximum allowable values for
the limit switches).
Limit switch passed: in "Control" or "Correction" operating mode
The limit switch position is passed by the necessary stopping
distance.
Set actual value is not executed.
Following acknowledgment of the error, it is possible to tra-
verse to the working range.
Alter value of software limit switch (MD22)
Disable limit switch monitoring!
(With the limit switches (MD21/22) disabled, the travel range
limits are established by the maximum allowable values for
the limit switches).
When operating in "Control" operating mode with soft limits dis-
abled, the traversing range beginning was passed.
The limit switch position is passed by the necessary stopping dis-
tance.
Following acknowledgment of the error, it is possible to traverse to
the working range.
When operating in "Control" operating mode with soft limits dis-
abled, the traversing range beginning was passed.
The limit switch position is passed by the necessary stopping dis-
tance.
Following acknowledgment of the error, it is possible to traverse to
the working range.
Message/
Display
Diagnostic
interrupt
i t
Diagnostic
interrupt
i t
Diagnostic
interrupt
i t
Diagnostic
interrupt
i t
FM 354 Servo Drive Positioning Module
t
t
t
t

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading