Function

3 .14 Relay outputs RO 1 and RO 2 function

The function of digital outputs RO 1 and RO 2 can be adjusted using BCSoft.
Signal at RO 1 or RO 2
CLOSED position
Low-fire rate position (low)
Intermediate position (middle)
OPEN position (high)
Freely programmable position
Faults and warnings
Fault
Manual mode
Ready
None
1)
These warnings are displayed as positioning errors in BCSoft.
IC 40 · Edition 07.18
Further setting options
equal to =
greater than or equal to > =
equal to or less than < =
Minimum and maximum value [°,%]
Reference switch drift > 5%
1)
Reference switch drift > 10%
1)
Reference switch does not open
Reference switch does not close
Internal temperature > 90°C
Analogue input IN < 4 mA
Service note
Relay switches when valve between min. and max.
1)
Faults are always signalled, warnings are signalled
1)
depending on the selection in BCSoft (see Inputs/
Outputs, 54 (Warnings and faults)
Only faults are displayed
Device is in Manual mode
Relay drops out in the event of: faults (not in the event
of warnings), Manual mode, zero position check,
calibration, no mains voltage
Relay output has no function
Remarks