8.6.3 Relay Function Static / Flashing

Relay 3:
The parameter setting "No" (cannot be changed).
The function "Flashing" offers a connection option for warning devices to improve visibility. The frequency is
about 1 second with an impulse / pause rate of 1:1.
If "Flashing" is set, the output circuit mustn't be used as a safe output any more.
The combination of relay mode energized with flashing operation makes no sense and is therefore suppressed.
Symbol
Description
No
Function

8.6.4 Alarm Quantity

In some applications it is necessary that the relay switches only at the n
of active alarms necessary for relay tripping. For safety related applications, the relay must always switch on
the first alarm.
Symbol
Description
1
No. of Alarms

8.6.5 Horn Function

Relay 3:
The parameter setting cannot be changed.
The horn function of the alarm relay is activated if at least one of the two parameters (time or assignment to
digital input) is set. The horn function retains its functionality even for alarms in latching mode.
This feature is not allowed for safety-related alarm messages because the output is resettable.
Symbol
Description Default
Recurrence Mode
Time
DI
Horn function resettable:
The activated horn can be reset with this function.
The following possibilities to acknowledge are available for the alarm relay as horn relay:
By pressing the left button (ESC). Only available in starting menu.
Automatic reset at the end of the preset time (active, if value > 0).
By an external pushbutton (assignment of the appropriate digital input DI 1-n).
Due to fixed polling cycles, external buttons must be pressed for a few seconds before the reaction occurs.
®
PolyGard
is a registered trademark of MSR
Phone 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
®
2
Default
Function
Yes
= Relay function flashing in case of alarm
No
No
= Relay function static in case of alarm
Default
Function
1
1 = Number of pending alarms for triggering the alarm relay
Function
No = Automatic reset of the relay after time has expired.
No
Yes = Recurrence function
Enter time for automatic reset function or recurrence function in s
0
0 = No reset function
0
0 – 2 = Assignment, which digital input resets the relay
Page
17
Flashing
No
Alarm Quantity
1
th
alarm. Here you can set the number
Time- Recurr.- DI
0s
No
0
Specification subject to change without notice
GAMGC2-K_E_0320