9.8 Safety

9.8.1 High Voltage Test

Carry out a high voltage test by short-circuiting terminals
9
9
U, V, W, L
, L
1
2
380-500 V frequency converters and 2.525 kV DC for
525-690 V frequency converters for one second between
this short-circuit and the chassis.
WARNING
When running high voltage tests of the entire instal-
lation, interrupt the mains and motor connection if the
leakage currents are too high.

9.8.2 EMC Grounding

Proper EMC grounding practice
Respect safety grounding.
Keeping the ground connection as short as
possible results in the best EMC performance.
Wires with greater square have a lower
impedance and better EMC grounding.
In case where more devices with metal cabinets
are used, mount them on common metal
mounting plate to improve EMC performance.
NOTICE
If necessary, use washers for fastening bolts, e.g. in case
of painted parts.
142
Power Size [kW]
Voltage [V]
0.37-
0.75
1.1-1.5
2.2-4
5.5-7.5
11-75
1.1-7.5
525-690
11-30
525-690
37-45
525-690
and L
. Energise maximum 2.15 kV DC for
3
®
VLT
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
1 cable [m]
400
150
500
150
400
150
500
150
400
150
500
150
400
150
500
150
400
150
500
150
100
150
150
CAUTION
POTENTIAL HAZARD IN THE EVENT OF INTERNAL
FAILURE
Risk of personal injury when the frequency converter is
not properly closed.

9.8.3 ADN-compliant Installation

Units with ingress protection rating IP55 (NEMA 12) or
higher prevent spark formation, and are classified as
limited explosion risk electrical apparatus in accordance
with the European Agreement concerning International
Carriage of Dangerous Goods by Inland Waterways (ADN).
For units with ingress protection rating IP20/Chassis, IP21/
NEMA 1, or IP54, prevent risk of spark formation as follows:
MG33BF02 - Rev. 2013-12-20
2 cables [m]
3 cables [m]
45
8
7
4
45
20
45
5
45
20
45
20
45
20
45
20
75
50
75
50
50
33
75
50
75
50
Before applying power, ensure all safety covers
are in place and securely fastened.
Do not install a mains switch
Ensure that 14-50 RFI Filter is set to [1] On.
Remove all relay plugs marked "RELAY". See
Illustration 9.56.
Check which relay options are installed, if any.
The only permitted relay option is Extended Relay
Card MCB 113.
4 cables [m]
6
3
8
4
11
6
11
11
37
37
25
37
37