Danfoss VLT AutomationDrive FC 301 Design Manual page 153

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Application Examples
Application Example
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 10.15 Using SLC to Set a Relay
®
VLT
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
Parameters
Function
Setting
7-00 Speed PID
[2] MCB 102
Feedback Source
17-11 Resolution
1024*
(PPR)
13-00 SL
[1] On
Controller Mode
13-01 Start
[19] Warning
Event
13-02 Stop
[44] Reset
Event
key
13-10 Comparat
[21] Warning
or Operand
no.
13-11 Comparat
[1] ≈*
or Operator
13-12 Comparat
90
or Value
13-51 SL
[22]
Controller Event
Comparator 0
13-52 SL
[32] Set
Controller Action
digital out A
low
5-40 Function
[80] SL digital
Relay
output A
* = Default Value
Notes/comments:
Warning 90 will be issued when
the feedback signal from the
encoder does not correspond
to the reference. The SLC
monitors Warning 90 and in
the case that Warning 90
becomes TRUE then Relay 1 is
triggered.
External equipment may then
indicate that service may be
required.
MG33BF02 - Rev. 2013-12-20
10
10
151