Options and Accessories
1-00 Configuration
[1] Speed closed loop
Mode
1-01 Motor Control
[3] Flux with feedback
Principle
1-10 Motor
[1] PM, non salient SPM
Construction
1-24 Motor Current
Nameplate
1-25 Motor Nominal
Nameplate
Speed
1-26 Motor Cont. Rated
Nameplate
Torque
AMA is not possible on PM motors
1-30 Stator Resistance
Motor data sheet
(Rs)
30-80 d-axis Inductance
Motor data sheet (mH)
(Ld)
1-39 Motor Poles
Motor data sheet
1-40 Back EMF at 1000
Motor data sheet
RPM
1-41 Motor Angle Offset Motor data sheet (Usually zero)
17-50 Poles
Resolver data sheet
17-51 Input Voltage
Resolver data sheet
17-52 Input Frequency
Resolver data sheet
17-53 Transformation
Resolver data sheet
Ratio
17-59 Resolver Interface [1] Enabled
Table 11.3 Parameters to Adjust
11.2.4 VLT
®
Relay Card MCB 105
The Relay Option MCB 105 includes 3 pieces of SPDT contacts and must be fitted into option slot B.
Electrical Data
1)
Max terminal load (AC-1)
(Resistive load)
(Inductive load @ cosφ 0.4)
1)
Max terminal load (AC-15 )
Max terminal load (DC-1)
1)
(Resistive load)
1)
Max terminal load (DC-13)
(Inductive load)
Min terminal load (DC)
Max switching rate at rated load/min load
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately the kit
includes
•
Relay Module MCB 105
•
Enlarged LCP fixture and enlarged terminal cover
•
Label for covering access to switches S201, S202
and S801
•
Cable strips for fastening cables to relay module
®
VLT
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20
11
11
240 V AC 2 A
240 V AC 0.2 A
24 V DC 1 A
24 V DC 0.1 A
5 V 10 mA
6 min
-1
/20 s
-1
157