Danfoss VLT AutomationDrive FC 301 Design Manual page 155

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Options and Accessories
Digital input - terminal X30/1-4
Number of digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP (GND = 0 V)
Voltage level, logic'1' PNP (GND = 0 V)
Voltage level, logic '0' NPN (GND = 24 V)
Voltage level, logic '1' NPN (GND = 24 V)
Maximum voltage on input
Pulse frequency range
Duty cycle, min. pulse width
Input impedance
Analog input - terminal X30/11, 12
Number of analog inputs
Terminal number
Modes
Voltage level
Input impedance
Max. voltage
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
Digital outputs - terminal X30/6, 7
Number of digital outputs
Terminal number
Voltage level at digital/frequency output
Max. output current
Max. load
Max. capacitive load
Minimum output frequency
Maximum output frequency
Accuracy of frequency output
Analog output - terminal X30/8
Number of analog outputs
Terminal number
Current range at analog output
Max. load GND - analog output
Accuracy on analog output
Resolution on analog output
®
VLT
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20
3
X30.2, X30.3, X30.4
PNP or NPN
0-24 V DC
< 5 V DC
> 10 V DC
< 14 V DC
> 19 V DC
28 V continous
0-110 kHz
4.5 ms
> 2 kΩ
2
X30.11, X30.12
Voltage
0-10 V
> 10 kΩ
20 V
10 bit (+ sign)
Max. error 0.5% of full scale
FC 301: 20 Hz/ FC 302: 100 Hz
2
X30.6, X30.7
0-24 V
40 mA
≥ 600 Ω
< 10 nF
0 Hz
≤ 32 kHz
Max. error: 0.1 % of full scale
1
X30.8
0-20 mA
500 Ω
Max. error: 0.5 % of full scale
12 bit
153
11
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents