Ep3356-0022 - Technical Data - Beckhoff EP3356-0022 Documentation

1-channel precise load cell analysis resistor bridge, 24 bit
Hide thumbs Also See for EP3356-0022:
Table of Contents

Advertisement

2.2

EP3356-0022 - Technical data

Technical data
Number of inputs
Signal connection sockets [} 46] M12
Resolution
Conversion time
Nominal voltage
Distributed Clocks
selectable modes
Measuring error
Measuring range U
D
Measuring range U
ref
Supported nominal sensitivity
Min. strain gauge resistor
Input filter limit frequency
(hardware)
Filter (software)
Internal resistance
Special features
Sensor supply
Current consumption from U
(without sensor current)
Power supply connection
Permissible ambient temperature
during operation
Permissible ambient temperature
during storage
Vibration / shock resistance
EMC immunity/emission
Dimensions
Weight
Installation position
Protection class
Approvals
EP3356-0022
EP3356-0022
2, for 1 resistor bridge in full bridge technology
24 Bit, 32 bit presentation
0.1 ms...250 ms, configurable, max. 10,000 samples/s
24 V
(-15 %/+20 %)
DC
yes
yes (2)
<±0.01 % for the calculated load value in relation to the final load value
with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge
characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active.
Attention: Due to external influences such as temperature drifts [} 10]
and HF-disturbances may possibly occur a not insignificant error!
max. -27 mV...+27 mV typ. (see note [} 89] concerning voltage
measuring recommended: -25 mV...+25 mV rated voltage
max. -13.8 V...+13.8 V typ. (see note [} 89] concerning voltage
measuring recommended: -12 V...+12 V rated voltage
all, resolution of parameter: 0.01 µV/V
Recommended: 0.5 mV/V...4 mV/V
parallel operation of strain gauges only with suitable strain gauges
recommended
10 kHz low pass (-3 dB)
Present 50 Hz,
Configurable: 50/60 Hz FIR notch filter, IIR low pass 4-fold averager
>200 kΩ (U
), > 1 MΩ (U
ref
self-calibration, quadruple averager, dynamic filters, fast data sampling,
parallel connection
U
= 10 V (supplied by the EP3356)
ref
120 mA
S
feed: 1 x M8 male socket, 4-pin
downstream connection: 1 x M8 female socket, 4-pin
-25°C...+60°C
0°C ... +55°C (according to cULus, see UL Requirements)
-40°C...+85°C
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
126 mm x 60 mm x 40 mm
approx.. 450 g
variable
IP65, IP66, IP67 (according to EN 60529)
CE, UL
Version: 1.1.0
)
d
Product overview
9