Mounting and Cabling
4.3.4

Conductor losses 7/8"

In the case of the power cables ZK2030-xxxx-yyy, a total length of 15 m should not be exceeded at 16 A.
When wiring, note that with a rated voltage of 24 V the function of the modules can no longer be guaranteed
from a voltage drop of 6 V. Variations in the output voltage from the power supply unit must also be taken
into account.
Fig. 30: ZK2030-xxxx-yyy - Conductor losses
2
Alternatively, larger cable cross-section can be used, e.g. 2.5 mm
.
EP3356-0022
Version: 1.1.0
39