14) Parameter group 700: Error handling and protection functions

Fault history

Read only parameters, for inverter error codes:
Fault codes:
2:
Overcurrent Hardware
F708
3:
Overvoltage
Last fault
4:
Phaseloss input
5:
Inverter overload
6:
Undervoltage
7:
Inverter overtemperature
F709
8:
Motor overload
Fault last
11: External emergency STOP
but one
13: AUTOTUNING error
16: Overcurrent software
17: Motor phase unbalanced
F710
18: Analogue signal interruption
23: PID improper parameters
Fault last
45: MODBUS time-out
but two
49: Watchdog time-out

Error: event counter:

F720
Overcurrent
F721
Overvoltage
F722
Overtemperature
F723
Overload
Protection functions – configuration
Activation of phase-loss, under-voltage and temperature monitoring
F724
Input phase-loss monitoring
F725
Under-voltage monitoring
F726
Over-temperature monitoring
F727
Motorphase monitoring

Delay for inverter error trip

F728
Delay phase-loss detection (sec.)
F729
Delay for under-voltage detection (sec.)
F730
Delay for over-temperature detection (sec.)
F732
Threshold for under-voltage detection (V)
(DC-Link voltage)
Overcurrent detection via software
F737
Software controlled overcurrent detection
F738
Software current limit (rated current unit)
F739
SW over-current inverter-trip counter
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
(OC)
(OE)
(PF1)
(OL1)
(LU)
(OH)
(OL2)
(ESP)
(Err2)
(OC1)
(PF0)
AErr
ERR5
CE
ERR6
OC
OE
OH
OL1
Selection: 0: deactivated
Selection: 0: deactivated
Selection: 0: deactivated
Selection: 0: deactivated
Range: 0.1 - 60.0 sec.
Range: 0.1 - 60.0 sec.
Range: 0.1 - 60.0 sec.
Range: 0.1 – 450V
Selection: 0: deactivated
Range: 0.50 - 3.00
- 57 -
F711
Frequency at last fault (Hz)
F712
Current at last fault (A)
F713
DC-Link voltage at last fault (V)
F714
Frequency at fault last but one (Hz)
F715
Current at fault last but one (A)
F716
DC-Link voltage at fault last but one (V)
F717
Fault last but two (Hz)
F718
Current at fault last but two (A)
F719
DC-Link voltage at fault last but one (V)
Default setting: 1
1: activated
Default setting: 1
1: activated
Default setting: 1
1: activated
Default setting: 0
1: activated
Default setting: 0.5 sec.
Default setting: 5.0 sec.
Default setting: 5.0 sec.
230V inverter: 215 V
400V inverter: 400 V
Default setting: 0
1: activated
Default setting: 2.0