F124

Jog frequency (Hz)

F125
Accel. ramp – Jog Mode (sec.)
F126
Decel. ramp –Jog Mode (sec.)
There are two modes to activate the Jog frequency: Keypad-control, and terminal-control (programmable digital inputs
OP1...OP8 – configuration: F316...F323).
Keypad-control: With the inverter in STOP mode press
Jog frequency start/stop toggle (F132 must be configured in the proper way 1+x+x+x).
Terminal control: A proper configured digital input works as Jog frequency start/stop toggle
Remark: In Jog mode the "catch on the fly" function is deactivated
F127/F129

Cut-Off frequency A,B (Hz)

F128/F130

Cut-Off frequency window A,B (Hz)

Cut-Off frequency to avoid resonance problems – the inverter transits during accel. / decel. ramps through this frequency areas,
but it can not stay stable within this frequency ranges.

Display configuration:

F131
Display: Selection of operating
parameters to display during „START"
status (Motor running)
To display a specific parameter, just set Parameter F131 to one of the values in the table above, to display more parameters,
the sum of all values must be set in F131
The
key is used to cycle through the various selected parameter values
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
8) Parameter group 100: Basic parameters
Range: F112 - F111
Range:
0.1 – 3000 sec.
key, to display HF-0, in this condition the
Range: 0.00 - 650.0
Range: ±2.5 Hz
0:
Output frequency / parameter value
1:
Motor speed (rpm)
2:
Motor current
4:
Motor voltage
8:
DC-voltage
16:
PID control feed back
32:
Heatsink temperature
64:
Reserviert
128: Speed (linear - calculated
256: PID set-point
512:
1024:
2048:
4096:
8192:
- 34 -
Default setting: 5.00 Hz
Default setting: 0.2 - 3.7KW: 5.0 sec.
5.5 - 30KW: 30.0 sec.
KW: 60.0 sec.
> 37
key works as a
Default setting: 0.00 Hz
Default setting: 0.0 Hz
Default setting:
0+1+2+4+8=15
(frequeny+speed+motor-
voltage+motor-
current+DC-voltage)