Function mapping for digital input channels

F316
Function assignation to DI1
F317
Function assignation to DI2
F318
Function assignation to DI3
F319
Function assignation to DI4
F320
Function assignation to DI5
F321
Function assignation to DI6
F322
Function assignation to DI7
F323
Function assignation to DI8
Attention:
One function can be assigned to one single digital input only (no multiple inputs) If a function is already assigned to a
certain input (factory set), this assignment must be deleted (set assignment to 0), before assigning to another input.

Table of digital input functions

VALUE
Function
0
No function
1
START function
2
STOP function
3
Fix-frequency K1
4
Fix-frequency K2
5
Fix-frequency K3
6
Fix-frequency K4
7
RESET
8
STOP-DISABLE
9
EMERGENCY STOP
10
RAMPSTOP
11
JOG foreward
12
JOG reverse
13
Motorpotentiometer +
14
Motorpotentiometer -
15
Terminal "FWD"
16
Terminal "REV"
17
Terminal "X"
18
BIT1 Ramp set selection
19
Reserved
20
Reserved
21
Reference source
22-31
Reserved
32
FIRE pressure
33
FIRE MODE
34
BIT2 Ramp set selection
37
NTC / NO
38
PTC / NC
53
Watchdog
E800 – Rev.01 -D- SOFT Rev. 2.04
© 2015 EURADRIVES EURDIE GmbH
10) Parametergruppe 300: Digital I/O Konfiguration
DI1 – DI5(8)
Function mapping:
No function assigned, for unused inputs
The input starts the drive system – same as "RUN" on keypad
Input stops the system – same as "STOP" on keypad
15-Fix-programmed frequencies are selectable (see table below 300-1)
General reset, error reset – same as "STOP/RESET" on keypad
"Free STOP" system stops with inertia (logical inversion: F324)
Ext. Emerg. STOP signal,
ESP
Inverter holds the actual frequency, independent from other signals (except STOP
signal) – ramps are stopped
JOG control, see F124, F125 and F126 for parametrizing
Motorpotentiometer-function, to increase/decrease frequency, (with internal speed
reference F203=0 / 5, control parameter: F113, F210, F211).
Assignation of terminal function "FWD", "REV", and "X" (see two/three wire control –
parameter F208)
Selection of Acce./Decel. ramp set (BIT1) – (see table 300-2)
--
Selection of different speed reference sources - combinations (see F207)
To select "Fire Mode" pressure setpoint (parameter FA58).
Activation of the "FIRE MODE" (FA59)
Selection of Accel. / Decel. ramp set (BIT2) – (see table 300-2)
Motor heath monitoring via NTC / NO contact (KLIXON)
Motor heath monitoring via PTC / NC contact (KLIXON)
Watchdog control-pulse input
- 45 -
Default setting
11
Default setting
9
Default setting
15
0....53
Default setting
16
Default setting
7
Default setting
8
Default setting
1
Default setting
2
Description
on display (signal logic: F325)
(JOG-forward)
(EMERGENCY-STOP EXT.)
(TERMINAL "FORWARD")
(TERMINAL "REVERSE")
(RESET)
(STOP-DISABLE)
(START)
(STOP)