F136

Slip compensation in V/Hz mode

- This parameter compensates the load-depending slip of the asynchronus motor – it works only in the stable area of the motor
speed/torque characteristic
- during the "catch on the fly" process this function is deactivated
F137
Motor voltage increase in the
low frequency range (for V/Hz
mode only)
F138

Lineare increase

F139

Quadratic increase

Voltage increase on low frequencies is necessary to compensate the
stator copper resistance.
With F137=0
voltage increase is chosen, suitable for constant
linear
torque load.
increase, the right curve for load with quadratic
F137=1
quadratic
characteristic, like pump and fan.
F137=2, serves to possible to program a user specific V/Hz curve – see table below
A total of 12 parameter are necessary to define the user specific curve (F140 bis F151) .
F140
User defined frequency F1
F141
Assigned motor voltage V1
F142
User defined frequency F2
F143
Assigned motor voltage V2
F144
User defined frequency F3
F145
Assigned motor voltage V3
F146
User defined frequency F4
F147
Assigned motor voltage V4
F148
User defined frequency F5
F149
Assigned motor voltage V5
F150
User defined frequency F6
F151
Assigned motor voltage V6
Remark: V1<V2<V3<V4<V5<V6,F1<F2<F3<F4<F5<F6.
If F137=3, the slip compensation works in automatic – correct setting
for all motor parameter is necessary to guarantee correct operation –
AUTOTUNING may be used to find motor parameters, like
inductance and stator resistance (see parameter group 8).
WARNING!! High voltage BOOST on low speed
may result in inverter over-current trip and/or
motor overheating
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
8) Parameter group 100: Basic parameters
Range: 0 - 10%
Selection: 0:
Linear
1:
Quadratic
2:
User defined (6 - Point)
3: Automatic
Range:
1 - 20
Selection:
1 - 6
F141
Range: 0 - F142
Range: 0 - 100%
Range:F140 - F144
Range: 0 - 100%
Range: F142 - F146
Range: 0 - 100%
Range: F144 - F148
Range: 0 - 100%
Range: F146 - F150
Range: 0 -100%
Range: F148 - F118
Range: 0 - 100%
Voltage (%)
- 36 -
Default setting: 0
Default setting: 3
Werk: 0.2-3.7 kW : 7
Default setting: 1
U
16
1
1
6
F140
Knee-frequency
Voltage increase
linear/quadratic/BOOST
Default setting: 1.00
Default setting: 4
Default setting: 5.00
Default setting: 13
Default setting: 10.00
Default setting: 24
Default setting: 20.00
Default setting: 45
Default setting: 30.00
Default setting: 63
Default setting: 40.00
Default setting: 81
V6
V5
V4
V3
V2
V1
F1 F2
F3
F4
F5
User p
rogrammable curve
5.5-30 kW : 6
37-75 kW
: 5
> 90 kW: 3
f
F6 Frequency (Hz)