Analogue input channels:

E800 SIZE
E1...E6
have two independent analogue input channels
Signal level configuration is done by hardware setting on the control board, and corresponding parameter setting.
For software parameter setting see: 11) Parameter group 400: Configuration of analogue I/O channels
AI1
Voltage signal input: 0....10V
AI2
Voltage/Current signal input: to configure for 0...5V, 0...10V or 0....20 mA - (4...20 mA: offset, to set via software
parameter – F406, F408) – (factory-default setting 0....20 mA)
AI2
Configuration of
Input impedance with voltage signal: 10 kOhm
Apparent ohmic resistance with current control: 500 Ohm
E800 – Rev.01 -D- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
E1 - E6:
- 24 -
AI1
and AI2, both have a resolution of 12 Bit.