F113
Internal speed reference (Hz)
Virtual internal speed reference, it is selectable in the same way, as any external speed reference (see F203, F204). If
selected, after the START command, the inverter will reach this speed value.
F114
Acceleration ramp 1 (sec.)
F115
Deceleration ramp 1 (sec.)
F116
Acceleration ramp 2 (sec.)
F117
Deceleration ramp 2 (sec.)
Acceleration ramp: Time to reach 50 Hz, or F-max (it depends on F119)
Deceleration ramp: Time, to decelerate to 0 Hz, referred to 50 Hz, or F-max (depending on F119)
The second ramp set is selectable via programmable digital input (OP1..OP8) - (F316~F323).
F119
Reference for Accel./Decel. ramp
time
If F119=0, ramp time is the duration from 0 Hz to 50 Hz, If F119=1 it is from 0 Hz to F-max.
F118
Knee frequency (Hz)
Frequency, corrisponding to the maximum inverter output voltage, the U/F characteristics reaches the horizontal range
Below the knee-frequency, the drive system operates in constant torque, above it works with constant power
ATTENTION!! Wrong setting of the Knee-Frequency may destroy the motor
F120

Dead time during reversion (sec.)

If activated (>0), the inverter will stop at 0Hz during the reversing cycle, indicated as
effect, if automatic frequency cycling is chosen).
This function may be useful, to avoid torque/current peaks during reversion
F122

Reverse operation disable

If F122=1 the inverter can operate in one rotating direction only, regardless of different other settings or control signals. A reversing
command will result in inverter STOP
If inverter rotation is set to "reverse" by parameter (F202=1), and F122 is set to "reversing disable", the inverter will not start
If "Catch on the fly" function is active, it will catch the motor, beginning with 0.0 Hz
F123
Reversing enable with combined
speed control
If in case of combined speed control, the speed result becomes negative (reverse rotation), this function may be used to
enable/disable the reverse rotation of the motor. If disabled, in case of negative speed, the inverter output 0,0 Hz (Parameter
F122=1 overwrites this setting)
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
8) Parameter group 100: Basic parameters
Range: F112 - F111
Range: 0.1 – 3000 sec.
Selection: 0: 0 ... 50.00Hz
1: 0 ... F-max
Range: 15.00 - 650.0
Range: 0.0 – 3000 sec.
Selection: 0: reversion enabled
1: reversion disabled
Selection: 0: disable
1: enable
- 33 -
Default setting: 50.00 Hz
Default setting: 0.2 - 3.7KW, 5.0 sec.
5.5 - 30KW, 30.0 sec.
> 37KW, 60.0 sec.
Default setting: 0.2 - 3.7KW, 5.0 sec.
5.5 - 30KW, 30.0 sec.
> 37KW, 60.0 sec.
Default setting: 0
Default setting: 50.00Hz
Default setting: 0.00 sec.
0.
on the display. (these parameter has no
Default setting: 0
Default setting: 0