Technical Data – Inverter Series E800 - EURA DRIVES E800 series Safety Instructions, Installation And Operating Manual

0,2kw – 110kw (ip20)
Table of Contents

Advertisement

Technical data – inverter series E800
Rated voltage
Power supply
Input frequency
EMC filter
Output voltage
Output frequency
Output
Resolution of output frequency
Overload capability
PWM control-modes
PWM frequency
V/Hz characteristic
Control mode
Torque boost
Motor data input
DC-Brake
Brake chopper
Display
7 Segment LED display -4- digit
Inverter control - Start/Stop
Digital control inputs
Speed reference signal
Reference analogue channels
Analogue outputs
I/O Channels,
control functions
Digitale outputs
Relays output
Interface
Special function - control options
Protection
Electrical protection functions
functions, incl.
fault memory
Thermal protection functions
Operating panel
Brake resistors
Optionals
Filter / chokes
PC-Link Software (via MODBUS)
Protection
Operating temperature
Environmental
Humidity
conditions
Elavation
Vibration
Power range
EMC
Standards
Safety
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
2) Product data / Product range
3-Phase 380...460V - 3 Ph. 220...240V - 1Ph. 220...240V - Tol. +/- 15%
44....67 Hz
Integrated for 2. Environment – C3 (up to 90 kW)
0.........U-input
0.........650 Hz
0,01 Hz
120% - 60 sec. / 10 Min
V/Hz - Mode
Permanentmagnet Synchronmotor control (Software option)
0,8...10 kHz
Linear, quadratic, and user-programmable curve
Automatic / Manual
Manual input / intelligent AUTOTUNING function
Freq. threshold, duration and intensity programmable
Integrated chopper transistor (Brake resistors – see product table)
For programming and visualization of different operating parameters
To configure: terminals / operation panel / serial link
8 (5) digital inputs (HIGH/LOW configurable), pulse input
Potentiometer (on operating panel / Extern), analogue input (terminals),
operating panel keys, pulse input, serial link
2 Analogue channels 12 BIT 0...10V, 0..(4)20 mA (with programmable offset,
gain – to concatenate mathematically each other)
2 (1) analogue output channels, both programmable in gain, different
functions to assign (0...10V, 0..20 mA)
2 (1) digital outputs (different functions to assign)
1 switchover contact 5 A 230 V (programmable for different functions)
Serial link (MODBUS – ASCI/RTU)
Jog mode, 12V / 50 mA auxiliary power supply on terminals
PI-control
Fixed frequency control "Catch on the fly function", AUTORESET/RESTART
functions
Overvoltage, Undervoltage
Overcurrent, Overload, Motor-Overload, Output-short
Phaseloss, Motor-Phase imbalance
Heatsink overtemperature – Motor overtemperature (PTC/KLIXON),
2
Motor I
xt
Remote keypad / programming tool
High power resistors for heavy duty operation
PFC chokes – dv/dt limiting output filter - sinusfilter
Special tool for programming, control and diagnostic (parameter set memory)
IP20 – IP21 (optional)
-10......+50 °C
Max. 90 % not condensing, no corrosion
1000 m - 1% derating / 100m above
Max. 0,5 g
0,2......400 kW
EN61800-3(2004)
EN61800-5-1 2003
- 13 -

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents