Sample Set-Up For Inverter, 400V - Framesize; 2014 Euradrives Europe Gmbh - EURA DRIVES E800 series Safety Instructions, Installation And Operating Manual

0,2kw – 110kw (ip20)
Table of Contents

Advertisement

Sample set-up for inverter, 400V - framesize

If parameter status is unknown, factory reset is recommended: Set parameter F160 = 1
Analogue speed reference 0....10V (potentiometer) through input channel
START/STOP command and inversion through terminal signals: set F208=2 (two wire control)
Fault signalling on relays contact: F300=1 (already default set)
„Inverter enabled" message on
Frequency indication output:
E800 / 3000 – Rev.04 -EN- SOFT Rev. 3.04
© 2014 EURADRIVES EUROPE GmbH
4) Electrical wiring of E800 inverters
E6
DO1
F301=14 (already default set)
AO1
0...10V = 0-50 Hz F423=1, F431=0 (already default set)
- 22 -
AI1:
Set F203=1