5) Steuerhardware und Hardware-Konfiguration der I/O Steuerkanäle
E1 - E6:

Digital output channels:

Inverters of the E800 series, SIZE
E1...E6
have one relay contact output, and one open collector output DO1, both are
free programmable for different functions, assignation codes are set in parameters F300 – F301.
TA-TB-TC Relay output: isolated switch over contacts, max. contact-load: 2A 230V (F300)
DO1 Digital output: OPEN COLLECTOR, referred to CM - U/High=24V, max. sink-current 100mA. (F301)
E1 - E6:

Analogue output channels:

One analogue output channels is available on inverters E800 SIZE
E1-E6:
AO1.
Different functions can be mapped to
this channels
AO1
: To configure for voltage or current signal – function assignation code in parameter F431
Software parameter F423...F426, for signal type configuration – see chapter: Parameter group 400
Hardware setting for
AO1
only (voltage/current signal
selection):
E800 – Rev.01 -D- SOFT Rev. 2.04
- 25 -