Control Terminal Function And Factory Default Configuration; 2014 Euradrives Europe Gmbh - EURA DRIVES E800 series Safety Instructions, Installation And Operating Manual

0,2kw – 110kw (ip20)
Table of Contents

Advertisement

Control terminal function and factory default configuration

Terminal
Type
Description
Programmable
DO1
digital output 1
Programmierbarer
DO2
Digitalausgang 2
Digital Relays
TA TB
output - isolated
TC
switchover contact
Programmable
AO1
analogue output 1
Programmable
AO2
analogue output 2
10V, ref. to
10V
processor- GND
Programmable
AI1
analogue input 1
Programmable
AI2
analogue input 2
Analogue
GND
GROUND
Isolated 24V power
24V
supply
Programmable
DI1
digital input 1
DI2
Programmable
digital input 2
DI3
Programmable
digital input 3
DI4
Programmable
digital input 4
Programmable
DI5
digital input 5
Programmable
DI6
digital input 6
Programmable
DI7
digital input 7
Programmable
DI8
digital input 8
Common potential
CM
digital I/O
Differential signal,
A+
positive
Differential signal,
B-
negative
E800 / 3000 – Rev.04 -EN- SOFT Rev. 3.04
© 2014 EURADRIVES EUROPE GmbH
4) Electrical wiring of E800 inverters
Hardware data
Open-Collector output, max. 100mA-24V
(referred on CM)
Open-Coll. output max. 100 mA-24V
(referred to CM
(Size C3-C6 only)
TC=COMMON TB=NORMAL CLOSED
TA=NORMAL OPEN
Max. Contact load:
Inverter 22kw and
below: 2A/230VAC
Inverter above 22
kW: 5A/230V
To configure for voltage/current signal
(reference: analogue ground GND)
For current signal: set SWITCH to „I"
Current signal (referred on GND)
size C3-C6 only)
10V supply for potentiometer or similar,
max. current 20 mA
Set-point – current/voltage input
for configuration see: (Hardware-
configuration of I/O channels)
Microprocessor ground, reference point
for all analogue signals
24±1.5V, to CM; limited to 50mA, for
powering of digital I/Os
All digital I/O are floating, including 24V
and CM HIGH/LOW active,
hardwaremäßig umschaltbar (siehe:
Hardware und Hardware-Konfiguration der
I/O Kanäle).
(DI6-DI8 on size C3-C6 only)
Common terminal for 24V aux. supply –
digital I/O signals
Standard: TIA/EIA-485(RS-485)
Interface protokol: MODBUS
Bd.Rate: 1200/2400/4800/9600/19200/
38400/57600
- 21 -
Related
parameter
(F301)
Message F=>0Hz
(F302)
Message F>0HZ
(F300)
Fault signal
(F413---F426)
(F431)
(on
(F427----F430)
(F432)
0-20mA
(F400-F405)
0...10V
(F418)
(F406-F411)
(F419)
(F316)
(F317)
STOP external
(F318)
(F319)
(F320)
(F321)
enable
(F322)
(F323)
(F900-F905)
Factory DEFAULT
Output frequency
0...10V
Motor current
0..20 mA
JOG mode FWD
EMERGENCY
Terminal (FWD)
Terminal (REV)
RESET
Power stage
START
STOP
9600