9) Parameter group 200: Inverter control

START / STOP / running direction:

F200
START command source
F201
STOP command source
- F200 and F201 are used to set the mode for inverter starting and stopping – via keypad key, digital input on terminals,
MODBUS commands, or a combination of all three. All signals are dynamic, input pulses, are sufficient, to start/stop the inverter.
This parameters are valid only, if F208=0 (default), if F208>0, this setting will be ignored
F202

Rotation direction preset

If no other rotation direction signal (logic) present, the rotation depends on this parameter – e.g. in case of keypad control.
Otherwise the direction depends on logical function of more direction signals
If (F500=2) – automatic frequency cycling – this parameter is ignored

Selection of speed reference sources:

F203
Primary speed
reference source
"X"
F203=0: Inverter accelerates after the first START command to the frequency value F113, using
configured digital terminal inputs, the user can vary the frequency, after a STOP command, the last frequency value will be
automatically memorized. To activate the memorizing function in case of power-down too, it needs to set F220=1.
F203=1 - F203=2: this is the setting for speed reference through analogue channels AI1-AI2. Analogue channels may be
configured for 0..10V, -10V...+10V, or 0(4)..20mA (on 500 Ohm). Configuration via DIP Switches on control board (see chapter: 5
Hardware und hardware configuration of I/O channels). Default: AI1 = 0...10V, AI2 = 0...20 mA. To realize 4...20mA, an offset
can be programmed: F406=2V.
F203=3: Impulse train as speed reference. Max. 50 kHz, impulse input: OP1.
F203=4: Up to 16 fix programmed frequencies, selectable via programmable digital inputs OP1...OP8
F203=5: Same function as F203=0: Internal reference (F113), but no memory after STOP or power-down
F203=6: The keypad potentiometer works as speed reference signal (only for keypads with integrated potentiometer)
F203=9: PID controller output works as speed reference origin (for PID controller applications))
F203=10: Speed reference through serial link (MODBUS)
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
9) Parameter group 200: Inverter control
Selection: 0: Keypad only
1: Terminal input only
2: Keypad + terminal input
3: Serial link (MODBUS)
4: Keypad + terminal + serial link
Selection: 0: Keypad only
1: Terminal input only
2: Keypad + terminal input
3: Serial link (MODBUS)
4: Keypad + terminal + serial link
Selection: 0: forward
1: reverse
2: depending on terminal signals
Selection:
0:Internal reference (F113) with automatic memory
1: Analogue input AI1
2: Analogue input AI2
3: Pulse input OP1
4: Fix-frequencies, terminal control (digital inputs)
5: same as 1, (F113) but no memory
6: Potentiometer in keypad (AI3)
7: reserved
8: reserved
9: PID controller output
10: MODBUS data
- 38 -
Default setting: 4
Default setting: 4
Default setting: 0
Default setting: 0