Parameter Group 100: Basic Parameters - EURA DRIVES E800 series Safety Instructions, Installation And Operating Manual

0,2kw – 110kw (ip20)
Table of Contents

Advertisement

Parameter group 100: Basic parameters

8)
F100
Password
-If F107=1 (password enabled): enter correct password, to unlock parameter modification function. Incorrect password results in
on the display
Err1
F102
Rated inverter current (A)
F103
Rated inverter power (KW)
F105
Software Version No.
F106
Control algorythm
2: V/Hz Modus funktioniert auch bei mehreren parallel geschalteten Motoren
6: * Optional software for synchronus motor comtrol (permanent magnet motor)
Attention!!
All motor parameters must be set precisely, to guarantee correct function. Especially in syncronus motor control mode
(F106=6) we recommend to run the AUTOTUNING routine (see: parameter group 800)
The V/Hz mode is recommendet for simple drives, including applications with quadratic torque characteristic (pump –
fan). F137 defines the different V/Hz characteristics
Inverter rated power should match the motor power
F107
Activation of password
protection (for parametrizing)
F108
Password setting
F109
Start – frequency (Hz)
F110
Start – frequency duration (sec.)
The inverter always starts running with the selected Start-frequency, if the target frequency is lower than the Start-frequency,
F109 will be ignored.
After the inverter gets a START command, it will remain at the Start-frequency, (set in F110), for the time, set in F111. After the
delay, it will proceed with the acceleration ramp to reach the final frequency. The acceleration ramp does not take into account
the start frequency delay time
The Start-frequency value is independent and not limited by the minimum frequency F112. In case F109 is lower, than F112, the
inverter will start running with the values in F109 and F110. After the inverter reached the minimum frequency F112, the values
F111 and F112 are considered as frequency limits.
It is recommended, to chose Start-frequency lower than maximum frequency (F111).
F111
Maximum frequency (Hz)
F112
Minimum working frequency (Hz)
The parameter F111 limits the inverter output frequency
In SENSORLESS VECTOR mode it is recommended to limit the maximum frequency to 150 Hz
The parameter F112 defines the minimum allowed output frequency. If speed reference corresponds to frequency lower than
the value in F112, the inverter stops.
WARNING!! Continuous operation at low speed may overheat the motor – forced ventilation is recommend
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
8) Parameter group 100: Basic parameters
Range: 0 – 9999
Range: 1.0 – 800.0
Range: 0.2 – 800.0
Range: 1.00 - 10.00
Selection: 2: V/Hz
3: Reserved
4: Reserved
5: Reserved
6: Synchronus motor control *
Selection: 0: No password protection
1: Password protection
Range: 0 - 9999
Range: 0.00 - 10.00 Hz
Range: 0.0 - 10.0 sec.
Range: F113 - 650.0 Hz
Range: 0.00 - F113 Hz
- 32 -
Factory set, depending on model, read only
Factory set, depending on model, read only
Factory set, depending on model, read only
Default setting: 0.00 Hz
Default setting: 0.0 sec.
Default setting: 50.00Hz
Default setting: 0.50Hz
Werkspasswort: 8
(2.04)
Default setting: 2
Default setting: 0
Default setting: 8