F209
"STOP" mode selection
If F208=1: STOP command disables the final stage, motor stops uncontrolled by inertia
F210
Frequency
Motorpotentiometer control via keypad/terminals
F211
Variation speed in Motorpotentiometer
control mode via keypad/terminals
If F203=0/5: Inverter starts with initial frequency F113 (memory with F203=0) – F220=1, to memorize with power-down too
F212

Status memory with (208=3)

If activated, after power down or reset, the inverter will restart with the same status, as before (the previous start impulse
forward/reverse was memorized)
F213

Autostart after power-down

F214

Inverter-Error AUTO-RESET

F215
Power-on Autostart delay (sec.)
F213=1 will force the inverter to restart automatically in case of power off. On power-on, the inverter will restart with the same
conditions, as before (frequency/direction). F215 defines the delay time for power-on autostart.
Power-on autostart works only with F208=0 (dynamic start command)
F214=1 will cause an automatic reset in case of inverter error. F217 is the delay time for error-reset, while F215 works as delay
time for restart after error-reset.
Autostart is performed only if error occurs during START condition (motor running), in case of STOP condition, only error-reset
will be done.
In case of deactivated automatic error-reset, manual reset (keypad/terminal signal) must be done
F216
Number of error-reset tentative
F217
Delay time for error-reset
F219
EEprom write protection under MODBUS control
Please note that F219, the EE-prom write protection it is activated by default (to prevent EE-prom from getting destroyed due to
repetitive write operations). With this configuration all data sent by MODBUS are stored in the RAM only and get lost after
power-down.
If inverter works with continuously varying parameter values, like speed reference, it is recommended, to work in the RAM only.
F220
Memory function for speed and rotation direction in case of
power-down
Valid in case of internal speed reference (F113), (F155 – F156)
F277
Acceleration time 3 (sec.)
F278
Decelaration time 3 (sec.)
F279
Acceleration time 4 (sec.)
F280
Decelaration time 4 (sec.)
Alternative ramps, selectable via terminal commands, in the same way as Accel./Decel time 1/2
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
9) Parameter group 200: Inverter control
Selection: 0: STOP controlled by deceleration ramp
1: Free-stop (uncontrolled)
resolution
with
Range: 0.01 - 2.00 Hz
Range: 0.01 - 100.0 Hz/sec.
Selection: 0: deactivated
Selection: 0: deactivated
Selection: 0: deactivated
Bereich: 0.1...3000.0 sec.
1: activated
1: activated
1: activated
Selection: 0 - 5
Range: 0.0 - 10.0 sec.
Selection: 0: deactivated
1: activated
Selection: 0: deactivated
1: activated
Range: 0,1 – 3000sec.
- 42 -
Default setting: 0
Default setting: 0.01 Hz
Default setting: 5.00 Hz/sec
Default setting: 0
Default setting: 0
Default setting: 0
Default setting: 60.0
Default setting: 0
Default setting: 3.0 sec.
Default setting: 1
Default setting: 0
Default setting:
depending on
inverter size