Recommended Cable Cross Sections, Fuses,; Earth/Ground Connection; Minimum Earth/Ground Wiring Cross Section – For Terminal Connection; 2014 Euradrives Europe Gmbh - EURA DRIVES E800 series Safety Instructions, Installation And Operating Manual

0,2kw – 110kw (ip20)
Table of Contents

Advertisement

Recommended cable cross sections, fuses,

Modell
Input
current
A
E800-0007 T3
E800-0015 T3
E800-0022 T3
E800-0030 T3
E800-0040 T3
E800-0055 T3
E800-0075 T3
E800-0110 T3
E800-0150 T3
E800-0185 T3
E800-0220 T3
E800-0300 T3
E800-0370 T3
E800-0450 T3
E800-0550 T3
E800-0750 T3
E800-0900 T3
Steuerleitungen
alle
Framesizen

Earth/ground connection

Minimum earth/ground wiring cross section – for terminal connection
Motor wiring section: S (mm
S
16<S
35<S
Minimum earth/ground wiring cross section – for chassis connection (on designed "G"
"GND" "GROUND" connection points)
Motor wiring section: S (mm
S
E800 / 3000 – Rev.04 -EN- SOFT Rev. 3.04
© 2014 EURADRIVES EUROPE GmbH
4) Electrical wiring of E800 inverters
Cable cross section
2
(mm
AWG)
Terminal tightening
torque
2
mm
/ AWG / lbs/inch
2,4
4,6
2,5 /
AWG14 /10
7
9
11
2,5 /
AWG12 /10,5
16
4 /
AWG10 /19
20
29
6
AWG8 /30,4
37
10
AWG6 /30,4
45
54
72
85
110
132
180
220
0,75-1
AWG20 /2,7
2
)
Minimum earth wiring cross ection
16
35
2
)
Minimum earth wiring cross ection
16
terminal tightening torque
Input fuses
IEC
UL-Class T (A) Bussmann-Type
60269
gG (A)
10A
16A
25A
35A
50A
16
16
63A
25
80A
35
125A
35
50
160A
95
200A
120
250A
= S
min 16
Min S/2
AWG8 / 6,2
= S
- 19 -
10A
JJS10
15A
JJS15
20A
JJS20
30A
JJS30
40A
JJS40
50A
JJS50
60A
JJS60
80A
JJS80
90A
JJS90
125A
JJS125
175A
JJS175
200A
JJS200
250A
JJS250
2
/PE/E (mm
)
2
/PE/E (mm
)