11) Parameter group 400: Analogue I/O channel configuration

Analogue output configuration

F423
Signal type configuration output
current/voltage signal
F424
Inverter output frequency assigned to
minimum output signal on
F425
Inverter output frequency assigned to
maximum output signal on
F426
Gain factor
AO1
*) The DIP-SWITCH U/I must be set, to get current signal on AO 1 output – see chapter 5) Control hardware and IO/
channel configuration
F427
Signal type configuration output
current signal only
F428
Inverter output frequency assigned to
minimum output signal on
F429
Inverter output frequency assigned to
maximum output signal on
F430
Gain factor
AO2
(AO2 for inverter size C3-C6 only)
F431
Assignation of operating
parameters
to
AO1
F432
Assignation of
operating parameters
to
AO2
F433
Multiplier for motor voltage meter
F434
Multiplier for motor current meter
F437
Filter factor analogue output
Assignation to motor current: The range 0...100% corresponds to 0....2x inverter rated current
Assignation to motor voltage: The range 0...100% corresponds to 0.....motor rated voltage (230 / 400V)
E800 – Rev.01 -EN- SOFT Rev. 2.04
© 2015 EURADRIVES EUROPE GmbH
AO1, AO2
Selection: 0=0...5V
AO1
Range: 0.0...F425
AO1
Range: F424...F111
AO1
Range: 0...120%
AO2
Selection: 0=0...20 mA
Range: 0.0...F429
AO2
Range: F428...F111
AO2
Range: 0...120%
Selection: 0=Motor frequency
1=Motor-current normalized on 2xI-n)
2=Motor-voltage (normalized on 230/400V)
3=AI1
4=AI2
5=Reserved
6=Reserved
7=Set via MODBUS
8=Target frequency
9=Calculated speed
Range: 0.01...5* rated value
Range: 1....100
- 50 -
1=0...10V, 0...20mA *
2=4...20mA *
1=4...20mA
Default setting: 1
Default setting: 0.05 Hz
Default setting: 50.00 Hz
Default setting: 100
Default setting: 0
Default setting: 0.05 Hz
Default setting: 50.00 Hz
Default setting: 100
Default
setting: 0
Default
setting: 1
Default setting: 2.0
Default setting: 2.0
Default setting: 10