Information List - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.9 Undervoltage-controlled reactive power protection (27/Q)
Addr.
Parameter
5521
Recl. release
5522
U> Reclose
5523
T Reclose
5524
Pos. f-diff
5525
Neg. f-diff
5526A
Incl. 27/Q Trip

Information List

2.9.4
No.
Information
6401
>27/Q Block
6411
27/Q OFF
6412
27/Q block
6413
27/Q ACT
6421
27/Q Gen TRIP
6422
27/Q Grid TRIP
6423
27/Q PICKUP
6424
Reclosure rel.
6425
27/Q blk.b.Inr.
146
C
Setting Options
OFF
ON
10.00 .. 210.00 V
0.00 .. 3600.00 sec
0.01 .. 5.00 Hz
-5.00 .. -0.01 Hz
NO
YES
Type of
Comments
Informa-
tion
SP
>QV-Protection Blocked
OUT
27/Q -Protection off
OUT
27/Q -Protection blocked
OUT
27/Q -Protection active
OUT
27/Q -Protection Gen TRIP
OUT
27/Q -Protection Grid TRIP
OUT
27/Q-Protection PICKUP
OUT
Reclosure release
OUT
27/Q pickup blocked by Inrush
Default Setting
Comments
OFF
Reclosure release
95.00 V
Voltage threshold for reclo-
sure rel.
0.00 sec
Reclosure Delay Time
0.05 Hz
Pos. f-diff threshold for
reclosure rel.
-2.50 Hz
Neg. f-diff threshold for
reclosure rel.
NO
Include 27/Q Trip for reclo-
sure rel.
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017