Information List - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.3 Directional Overcurrent Protection 67, 67N
Addr.
Parameter
1624
67N-1 Direction
1625
67N-TOC Direct.
1626
67N-3 Direction
1627A
67N-3 MEASUREM.
1628
67N-3 PICKUP
1629
67N-3 DELAY
1630
M.of PU TD
1631
I/IEp Rf T/TEp
1632A
67N-3 active
2.3.12

Information List

No.
Information
2603
67N-3 TRIP
2604
>BLK 67/67-TOC
2605
67N-3 BLOCKED
2606
67-3 BLOCKED
2614
>BLK 67N/67NTOC
2615
>BLOCK 67-2
2616
>BLOCK 67N-2
2617
>BLOCK 67-3
2618
>BLOCK 67N-3
2621
>BLOCK 67-1
2622
>BLOCK 67-TOC
2623
>BLOCK 67N-1
2624
>BLOCK 67N-TOC
2628
Phase A forward
2629
Phase B forward
2630
Phase C forward
2632
Phase A reverse
2633
Phase B reverse
2634
Phase C reverse
2635
Ground forward
2636
Ground reverse
2637
67-1 BLOCKED
104
C
Setting Options
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Fundamental
True RMS
0.50 .. 35.00 A; ∞
0.00 .. 60.00 sec; ∞
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
always
with 79 active
Type of
Comments
Informa-
tion
OUT
67N-3 TRIP
SP
>BLOCK 67/67-TOC
OUT
67N-3 is BLOCKED
OUT
67-3 is BLOCKED
SP
>BLOCK 67N/67N-TOC
SP
>BLOCK 67-2
SP
>BLOCK 67N-2
SP
>BLOCK 67-3
SP
>BLOCK 67N-3
SP
>BLOCK 67-1
SP
>BLOCK 67-TOC
SP
>BLOCK 67N-1
SP
>BLOCK 67N-TOC
OUT
Phase A forward
OUT
Phase B forward
OUT
Phase C forward
OUT
Phase A reverse
OUT
Phase B reverse
OUT
Phase C reverse
OUT
Ground forward
OUT
Ground reverse
OUT
67-1 is BLOCKED
Default Setting
Comments
Forward
67N-1 Direction
Forward
67N-TOC Direction
Forward
67N-3 Direction
Fundamental
67N-3 measurement of
∞ A
67N-3 Pickup
0.00 sec
67N-3 Time Delay
Multiples of PU Time-Dial
67N TOC
always
67N-3 active
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sj80Siprotec 4 7saj8

Table of Contents