Settings - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Pickup Values
You can set the pickup value for the reactive power stage at address 5511 Q> Pickup.
Example:
Q > 5 % of the supply system rating
V
= 100 V
Nomsec
I
= 1 A
Nomsec
this yields the (default) setting value Q> Pickup for Q> Pickup
100 V · 1 A · √3 · 0.05 = 8.7 VAR
At address 5512 U< Pickup, you can enter the pickup value for the voltage stage.
Delays
Address 5513 Delay Gen. CB is used to set the time delay for tripping the circuit breaker of the generation
facility, e.g. at the generator.
Enter the time delay for tripping the circuit breaker at the supply system connection point at address 5514
Delay Grid CB. Always set the delay time longer than delay time Delay Gen. CB.
Close Release
At address 5521 Recl. release the close release is switched ON or OFF.
At address 5522 U> Reclose you can specify the release voltage. Set the value to approx. 95 % of the rated
voltage value (default).
Specify the delay time for releasing the generator reconnection at address 5523 T Reclose.
Furthermore, enter the admitted deviation from the rated frequency. At address 5524 Pos. f-diff enter
the frequency deviation in positive direction and at address 5525 Neg. f-diff in negative direction. If the
measured frequency is within this range, this reconnection condition is satisfied.
Address 5526 Incl. 27/Q Trip determines whether the tripping indication of the QU protection is taken
into account for the reconnection release.

Settings

2.9.3
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding
secondary nominal current of the current transformer.
Addr.
Parameter
5501
27/Q-Protection
5502
I-Release
5503
Inrush blk
5504
Q> Direction
5511
Q> Pickup
5512
U< Pickup
5513
Delay Gen. CB
5514
Delay Grid CB
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
C
Setting Options
OFF
ON
1A
0.02 .. 0.20 A; 0
5A
0.10 .. 1.00 A; 0
NO
YES
Forward
Reverse
1A
1.70 .. 10000.00 VAR
5A
8.50 .. 50000.00 VAR
10.00 .. 210.00 V
0.00 .. 60.00 sec
0.00 .. 60.00 sec
2.9 Undervoltage-controlled reactive power protection (27/Q)
Default Setting
Comments
OFF
27 / Q dir. con. Protection
0.10 A
Current-Rel. for Trip and
Reclose
0.50 A
NO
blocking with inrush
Forward
Reactive power direction
8.70 VAR
Reactive power threshold
for pickup
43.50 VAR
85.00 V
Undervoltage threshold for
pickup
0.50 sec
Trip time delay generator
CB
1.50 sec
Trip time delay grid CB