Information List; Types Of Commands; Functional Description; Command Sequence - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.24 Breaker Control
substation. Furthermore, certain settings for the serial interface need to be made in the device (see SIPROTEC
4 System Description).
2.24.1.2

Information List

No.
Information
-
52Breaker
-
52Breaker
-
Disc.Swit.
-
Disc.Swit.
-
GndSwit.
-
GndSwit.
31000
Q0 OpCnt=
31001
Q1 OpCnt=
31008
Q8 OpCnt=

Types of Commands

2.24.2
In conjunction with the power system control several command types can be distinguished for the device:
2.24.2.1

Functional Description

Commands to the Process
These are all commands that are directly output to the switchgear to change their process state:
Switching commands for controlling the circuit breakers (not synchronized), disconnectors and ground
electrodes
Step commands, e.g. raising and lowering transformer LTCs
Set-point commands with configurable time settings, e.g. to control Petersen coils
Internal / Pseudo Commands
They do not directly operate binary outputs. They serve to initiate internal functions, simulate changes of
state, or to acknowledge changes of state.
Manual overriding commands to manually update information on process-dependent objects such as
annunciations and switching states, e.g. if the communication with the process is interrupted. Manually
overridden objects are flagged as such in the information status and can be displayed accordingly.
Tagging commands (for "setting") of the information value of internal objects, for example switching
authority (remote/local), settings group switching, data transmission block and deleting/presetting
metered values.
Acknowledgment and resetting commands for setting and resetting internal buffers or data states.
Information status command to set/reset the additional information "information status" of a process
object, such as:
Input blocking
Output blocking
2.24.3

Command Sequence

Safety mechanisms in the command sequence ensure that a command can only be released after a thorough
check of preset criteria has been successfully concluded. Standard Interlocking checks are provided for each
300
Type of
Comments
Informa-
tion
CF_D12
52 Breaker
DP
52 Breaker
CF_D2
Disconnect Switch
DP
Disconnect Switch
CF_D2
Ground Switch
DP
Ground Switch
VI
Q0 operationcounter=
VI
Q1 operationcounter=
VI
Q8 operationcounter=
SIPROTEC 4, 7SJ80, Manual