Siemens SIPROTEC 4 Manual page 490

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
5302
FUSE FAIL 3Vo
5303
FUSE FAIL RESID
5308A FFM Idiff (3ph)
5310
BLOCK PROT.
5401
FCT 81 O/U
5402
Vmin
5402
Vmin
5403
81-1 PICKUP
5404
81-1 PICKUP
5405
81-1 DELAY
5406
81-2 PICKUP
5407
81-2 PICKUP
5408
81-2 DELAY
5409
81-3 PICKUP
5410
81-3 PICKUP
5411
81-3 DELAY
5412
81-4 PICKUP
5413
81-4 PICKUP
5414
81-4 DELAY
5415A DO differential
5421
FCT 81-1 O/U
5422
FCT 81-2 O/U
5423
FCT 81-3 O/U
5424
FCT 81-4 O/U
5501
27/Q-Protection
5502
I-Release
5503
Inrush blk
490
Function
C
Setting Options
Meas-
10 .. 100 V
urem.Superv
Meas-
1A
0.10 .. 1.00 A
urem.Superv
5A
0.50 .. 5.00 A
Meas-
1A
0.05 .. 1.00 A
urem.Superv
5A
0.25 .. 5.00 A
Meas-
NO
urem.Superv
YES
81 O/U Freq.
OFF
ON
81 O/U Freq.
10 .. 150 V
81 O/U Freq.
20 .. 150 V
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
0.02 .. 1.00 Hz
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
27/Q
OFF
ON
27/Q
1A
0.02 .. 0.20 A; 0
5A
0.10 .. 1.00 A; 0
27/Q
NO
YES
Default Setting
Comments
30 V
Zero Sequence Voltage
0.10 A
Residual Current
0.50 A
0.10 A
Differential Current
Threshold (3phase)
0.50 A
YES
Block protection by FFM
OFF
81 Over/Under Frequency
Protection
65 V
Minimum required
voltage for operation
35 V
Minimum required
voltage for operation
49.50 Hz
81-1 Pickup
59.50 Hz
81-1 Pickup
60.00 sec
81-1 Time Delay
49.00 Hz
81-2 Pickup
59.00 Hz
81-2 Pickup
30.00 sec
81-2 Time Delay
47.50 Hz
81-3 Pickup
57.50 Hz
81-3 Pickup
3.00 sec
81-3 Time delay
51.00 Hz
81-4 Pickup
61.00 Hz
81-4 Pickup
30.00 sec
81-4 Time delay
0.02 Hz
Dropout differential
OFF
81-1 Over/Under
Frequency Protection
OFF
81-2 Over/Under
Frequency Protection
OFF
81-3 Over/Under
Frequency Protection
OFF
81-4 Over/Under
Frequency Protection
OFF
27 / Q dir. con. Protection
0.10 A
Current-Rel. for Trip and
Reclose
0.50 A
NO
blocking with inrush
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017