2.23.8.1
Functional Description
Metered Values for Active and Reactive Energy
Metered values of the real power W
hours primary or in kVARh, MVARh or GVARh primary, separately according to the input (+) and output (–), or
capacitive and inductive. The measured-value resolution can be configured. The signs of the measured values
appear as configured in address 1108 P,Q sign (see Section "Display of Measured Values").
2.23.8.2
Setting Notes
Setting of parameter for meter resolution
Parameter 8315 MeterResolution allows increasing the resolution of the energy metered values by the
Factor 10 or Factor 100 compared to the Standard setting.
2.23.8.3
Settings
Addr.
Parameter
8315
MeterResolution
2.23.8.4
Information List
No.
Information
-
Meter res
888
Wp(puls)
889
Wq(puls)
916
WpΔ=
917
WqΔ=
924
WpForward
925
WqForward
928
WpReverse
929
WqReverse
Commissioning Aids
2.23.9
In test mode or during commissioning, the device information transmitted to a central or storage device can
be influenced. There are tools available for testing the system interface (port B) and the binary inputs and
outputs of the device.
Applications
•
Test Mode
•
Commissioning
Prerequisites
In order to be able to use the commissioning aids described in the following, the device must be connected to
a control center via port B.
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
and reactive power (W
p
Setting Options
Standard
Factor 10
Factor 100
Type of
Comments
Informa-
tion
IntSP_Ev
Reset meter
PMV
Pulsed Energy Wp (active)
PMV
Pulsed Energy Wq (reactive)
-
Increment of active energy
-
Increment of reactive energy
MVMV
Wp Forward
MVMV
Wq Forward
MVMV
Wp Reverse
MVMV
Wq Reverse
) are acquired in kilowatt, megawatt or gigawatt
q
Default Setting
Comments
Standard
Meter resolution
Functions
2.23 Auxiliary Functions
297