Settings; Information List; Min/Max Measurement Setup; Functional Description - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

2.23.4.3

Settings

Addr.
Parameter
8301
DMD Interval
8302
DMD Sync.Time
2.23.4.4

Information List

No.
Information
833
I1 dmd=
834
P dmd =
835
Q dmd =
836
S dmd =
963
Ia dmd=
964
Ib dmd=
965
Ic dmd=

Min/Max Measurement Setup

2.23.5
Minimum and maximum values are calculated by the 7SJ80. Time and date of the last update of the values
can also be read out.
2.23.5.1

Functional Description

Minimum and Maximum Values
The minimum and maximum values for the three phase currents Ι
the three phase-to-phase voltages V
V
, the real power P, reactive power Q, and apparent power S, the frequency; and the power factor cos ϕ are
0
calculated as primary values (including the date and time they were last updated).
The minimum and maximum values of the long-term averages listed in the previous section are also calcu-
lated.
The minimum and maximum values can be reset at any time via binary inputs or by using the integrated
control panel or the DIGSI software. Additionally, the reset can be carried out cyclically, starting at a preset
point of time.
2.23.5.2

Setting Notes

Minimum and Maximum Values
The tracking of minimum and maximum values can be reset automatically at a programmable point in time.
To select this feature, address 8311 MinMax cycRESET should be set to YES. The point in time when reset is
to take place (the minute of the day in which reset will take place) is set at address 8312 MiMa RESET TIME.
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Setting Options
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
On The Hour
15 After Hour
30 After Hour
45 After Hour
Type of
Comments
Informa-
tion
MV
I1 (positive sequence) Demand
MV
Active Power Demand
MV
Reactive Power Demand
MV
Apparent Power Demand
MV
I A demand
MV
I B demand
MV
I C demand
, the positive sequence components Ι
xy
Default Setting
Comments
60 Min., 1 Sub
Demand Calculation Intervals
On The Hour
Demand Synchronization Time
, the three phase-to-ground voltages V
x
and V
1
Functions
2.23 Auxiliary Functions
,
x-N
, the displacement voltage
1
293

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sj80Siprotec 4 7saj8

Table of Contents