Information List - Siemens SIPROTEC 4 Manual

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Functions
2.1 General
Addr.
Parameter
6014
S2: x'
6015
S2: Line angle
6016
S2: Line length
6017
S2: Line length
6021
S3: RE/RL
6022
S3: XE/XL
6023
S3: x'
6024
S3: x'
6025
S3: Line angle
6026
S3: Line length
6027
S3: Line length
2.1.6.4

Information List

No.
Information
126
ProtON/OFF
356
>Manual Close
466.4010 Cmd Trip
501
Relay PICKUP
511
Relay TRIP
533
Ia =
534
Ib =
535
Ic =
561
Man.Clos.Detect
2720
>Enable ANSI#-2
4601
>52-a
4602
>52-b
16019
>52 Wear start
16020
52 WearSet.fail
16027
52WL.blk I PErr
16028
52WL.blk n PErr
18420
>Trip via BI
18421
Trip via GOOSE
18423
Direct Trip
18424
PI Trip NC
18425
>DDI Open
54
C
Setting Options
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
-0.33 .. 7.00
-0.33 .. 7.00
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
10 .. 89 °
0.1 .. 650.0 Miles
0.1 .. 1000.0 km
Type of
Comments
Informa-
tion
IntSP
Protection ON/OFF (via system port)
SP
>Manual close signal
IntSP
Trip via control command
OUT
Relay PICKUP
OUT
Relay GENERAL TRIP command
VI
Primary fault current Ia
VI
Primary fault current Ib
VI
Primary fault current Ic
OUT
Manual close signal detected
SP
>Enable 50/67-(N)-2 (override 79 blk)
SP
>52-a contact (OPEN, if bkr is open)
SP
>52-b contact (OPEN, if bkr is closed)
SP
>52 Breaker Wear Start Criteria
OUT
52 Wear blocked by Time Setting Failure
OUT
52 Breaker Wear Logic blk Ir-CB>=Isc-CB
OUT
52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir
SP
>Trip via Binary Input
ExSP
Trip via GOOSE
OUT
Direct Trip
OUT
PI Trip NC(ON,if Device ok & No Trip)
SP
>DDI Open status
Default Setting
Comments
0.1500 Ω/km
S2: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S2: Line angle
62.1 Miles
S2: Line length in miles
100.0 km
S2: Line length in kilometer
1.00
S3: Zero seq. compen-
sating factor RE/RL
1.00
S3: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S3: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S3: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S3: Line angle
62.1 Miles
S3: Line length in miles
100.0 km
S3: Line length in kilometer
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017