Directional limit line PHI CORRECTION
Dropout delay RESET DELAY
Limitation of the directional areas using α1 and α2
Angle tolerance
Direction Determination for all Types of Ground Fault with V0 ϕ / I0 ϕ Measurement
Direction measurement
Measuring principle
50Ns-1 element
Minimum voltage 50Ns-1 Vmin
V0 measured
3V0 calculated
Phase angle 50Ns-1 Phi
Delta phase angle 50Ns-1 DeltaPhi
50Ns-2 element
Minimum voltage 50Ns-2 Vmin
V0 measured
3V0 calculated
Phase angle 50Ns-2 Phi
Delta phase angle 50Ns-2 DeltaPhi
Angle tolerance
Angle tolerance
Angle correction for cable converter in two operating points F1/I1 and F2/I2:
Angle correction F1, F2
(for resonant-grounded system)
Current values Ι1, Ι for angle correction
for sensitive 1 A transformer
for sensitive 5 A transformer
for normal 1 A transformer
for normal 5 A transformer
Measurement tolerance
sensitive
non-sensitive
Note: Due to the high sensitivity, the linear range of the measuring input Ι
transformer is from 0.001 · Ι
tion can no longer be guaranteed.
EPTR Setting Ranges / Increments
Pickup current
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
0.0° to 5.0°
0.001 A to 1.600 A
0.005 A to 8.000 A
0.05 A to 36.00 A
0.25 A to 175.00 A
3 % of setting value or 1 mA
for Ι
= 1 A
Nom
for Ι
= 5 A
3 % of setting value or 5 mA
Nom
for setting values < 10 mA ca. 20 %
for Ι
= 1 A
3 % of setting value or 15 mA
Nom
for Ι
= 5 A
3 % of setting value or 75 mA
Nom
to 1.6 · Ι
. For currents greater than 1.6 · Ι
Nom
Nom
0.001 A to 2.400 A
for Ι
= 1 A
N
for Ι
= 5 A
0.005 A to 7.000 A
N
4.14 Ground Fault Detection (Sensitive/Insensitive)
-45.0° to +45.0°
Increments 0.1°
1 s to 60 s
Increments 1 s
1° to 15°
Increments 1°
3°
- Ι
and V
measured
N
N
- 3Ι
and 3V
calculated
0
0
V0 / Ι0 phase angle measurement
0.4 V to 50 V
Increments 0.1 V
10 V to 90 V
Increments 1 V
- 180° tos 180°
Increments 1°
0° bis 180°
Increments 1°
0.4 V to 50 V
Increments 0.1 V
10 V to 90 V
Increments 1 V
- 180° to 180°
Increments 1°
0° to 180°
Increments 1°
3°
Increments 0.1°
Increments 0.001 A
Increments 0.005 A
Increments 0.01 A
Increments 0.05 A
with integrated sensitive input
N
, correct direction determina-
Nom
Technical Data
Incre-
ments0.001 A
397