Type test (in acc. with IEC 60068-2-1 and -2, Test
Bd for 16 h)
Damp heat, steady state - Test Cab
IEC 60255-1 and IEC 60068-2-78.
Damp heat, cyclic - Test Db
IEC 60255-1 and IEC 60068-2-30
Permissible temporary operating temperature
(tested for 96 h)
Recommended for permanent operation (in acc.
with IEC 60255-6)
Limit temperatures for storage
Limit temperatures for transport
Storage and transport with factory packaging
Humidity
Permissible humidity
Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor
subject to large fluctuations in temperature that may cause condensation to occur.

Service Conditions

4.1.8
The protective device is designed for use in an industrial environment and an electrical utility environment.
Proper installation procedures should be followed to ensure electromagnetic compatibility (EMC).
In addition, the following is recommended:
All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protec-
tive device should, as a rule, be equipped with suitable surge suppression components.
For substations with operating voltages of 100 kV and above, all external cables should be shielded with
a conductive shield grounded at both ends. For substations with lower operating voltages, no special
measures are normally required.
Do not withdraw or insert individual modules or boards while the protective device is energized. In with-
drawn condition, some components are electrostatically endangered; during handling the ESD stand-
ards (for Electrostatic Sensitive Devices) must be observed. They are not endangered when inserted into
the case.

Constructive Design

4.1.9
Case
Dimensions
Device
7SJ80**-*B
7SJ80**-*E
Protection type acc. to IEC 60529
For equipment in the surface-mounting case
For equipment in flush mounting case
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
–25 °C to +85 °C oder –13 °F to +185 °F
40 °C, 93 % RH, 56 days
25 °C to/down 40 °C in 3 hr., > 93 % RH, dwell time 9 hr.
6 cycles
–20 °C to +70 °C oder –4 °F to +158 °F (clearness of the
display may be impaired from +55 °C or +131 °F)
–5 °C to +55 °C or +23 °F to +131 °F
–25 °C to +55 °C or –13 °F to +131 °F
–25 °C to +70 °C or –13 °F to +158 °F
Mean value per year ≤ 75 % relative humidity;
on 56 days of the year up to 93 % relative humidity;
condensation must be avoided!
Case
for panel surface mounting
for panel flush mounting
7XP20
see dimensional drawings, Section
IP 50
Front IP 51
Rear IP 50
Technical Data
4.1 General Device Data
4.25 Dimensions
Size
Weight
4.5 kg (9.9 lb)
1
/
6
4 kg (8.8 lb)
1
/
6