Functions, Settings, Information
F.2 Settings
Addr. Parameter
1705
Stop Time
1801
50c-2 PICKUP
1802
50c-2 DELAY
1803
50c-1 PICKUP
1804
50c-1 DELAY
1805
51c PICKUP
1806
51c TIME DIAL
1807
51c TIME DIAL
1808
50c-3 PICKUP
1809
50c-3 DELAY
1901
50Nc-2 PICKUP
1902
50Nc-2 DELAY
1903
50Nc-1 PICKUP
1904
50Nc-1 DELAY
1905
51Nc PICKUP
1906
51Nc T-DIAL
1907
51Nc T-DIAL
1908
50Nc-3 PICKUP
1909
50Nc-3 DELAY
2001
67c-2 PICKUP
2002
67c-2 DELAY
2003
67c-1 PICKUP
2004
67c-1 DELAY
2005
67c-TOC PICKUP
2006
67c-TOC T-DIAL
2007
67c-TOC T-DIAL
2008
67c-3 PICKUP
2009
67c-3 DELAY
2101
67Nc-2 PICKUP
2102
67Nc-2 DELAY
2103
67Nc-1 PICKUP
2104
67Nc-1 DELAY
2105
67Nc-TOC PICKUP
484
Function
C
Setting Options
ColdLoadPickup
1 .. 600 sec; ∞
ColdLoadPickup 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 50.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.30 sec
ColdLoadPickup 1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
ColdLoadPickup
0.05 .. 3.20 sec; ∞
ColdLoadPickup
0.50 .. 15.00 ; ∞
ColdLoadPickup 1A
1.00 .. 35.00 A; ∞
5A
5.00 .. 175.00 A; ∞ ∞ A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 35.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 7.50 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.30 sec
ColdLoadPickup 1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
ColdLoadPickup
0.05 .. 3.20 sec; ∞
ColdLoadPickup
0.50 .. 15.00 ; ∞
ColdLoadPickup
0.05 .. 35.00 A; ∞
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 50.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.10 .. 35.00 A; ∞
5A
0.50 .. 175.00 A; ∞ 10.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.30 sec
ColdLoadPickup 1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
ColdLoadPickup
0.05 .. 3.20 sec; ∞
ColdLoadPickup
0.50 .. 15.00 ; ∞
ColdLoadPickup 1A
1.00 .. 35.00 A; ∞
5A
5.00 .. 175.00 A; ∞ ∞ A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 35.00 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.00 sec
ColdLoadPickup 1A
0.05 .. 35.00 A; ∞
5A
0.25 .. 175.00 A; ∞ 7.50 A
ColdLoadPickup
0.00 .. 60.00 sec; ∞ 0.30 sec
ColdLoadPickup 1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
Default Setting
Comments
600 sec
Stop Time
10.00 A
50c-2 Pickup
50c-2 Time Delay
2.00 A
50c-1 Pickup
50c-1 Time Delay
1.50 A
51c Pickup
7.50 A
0.50 sec
51c Time dial
5.00
51c Time dial
∞ A
50c-3 Pickup
50c-3 Time Delay
7.00 A
50Nc-2 Pickup
50Nc-2 Time Delay
1.50 A
50Nc-1 Pickup
50Nc-1 Time Delay
1.00 A
51Nc Pickup
5.00 A
0.50 sec
51Nc Time Dial
5.00
51Nc Time Dial
∞ A
50Nc-3 Pickup
50Nc-3 Time Delay
10.00 A
67c-2 Pickup
67c-2 Time Delay
2.00 A
67c-1 Pickup
67c-1 Time Delay
1.50 A
67c Pickup
7.50 A
0.50 sec
67c Time Dial
5.00
67c Time Dial
∞ A
67c-3 Pickup
67c-3 Time Delay
7.00 A
67Nc-2 Pickup
67Nc-2 Time Delay
1.50 A
67Nc-1 Pickup
67Nc-1 Time Delay
1.00 A
67Nc-TOC Pickup
5.00 A
SIPROTEC 4, 7SJ80, Manual