Functions
2.6 Voltage Protection 27, 59
NOTE
i
i
If a setting is selected such that the dropout threshold (= pickup threshold · dropout ratio) results in a
greater value than 130 V/225 V, it will be limited automatically. No error message occurs.
Current Criterion for Undervoltage Protection
The 27-1 element and the 27-2 element can be supervised by the current flow monitoring setting. If the
CURRENT SUPERV. is switched ON at address 5120 (factory setting), the release condition of the current
criterion must be fulfilled in addition to the corresponding undervoltage condition, which means that a config-
ured minimum current (BkrClosed I MIN, address 212) must be present to make sure that this protective
function can pick up. Thus it can be achieved that pickup of the undervoltage protection drops out when the
line is disconnected from voltage supply. Furthermore, this feature prevents an immediate general pickup of
the device when the device is powered-up without measurement voltage being present.
NOTE
i
i
If parameter CURRENT SUPERV.is set to disabled at address 5120, the device picks up immediately if the
measuring-circuit voltage fails and the undervoltage protection is enabled. Furthermore, configuration can
be performed by pickup of measuring-circuit voltage or blocking of the voltage protection. The latter can be
initiated via device operation in DIGSI and via communication from the control center by means of a
tagging command for blocking the voltage protection. This causes the dropout of the pickup and parame-
terization can be resumed.
Please note that the pickup threshold BkrClosed I MIN (address 212) also affects the overload protection,
the cold load pickup function and the CB maintenance.

Settings

2.6.5
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
5001
FCT 59
5002
59-1 PICKUP
5003
59-1 PICKUP
5004
59-1 DELAY
5005
59-2 PICKUP
5006
59-2 PICKUP
5007
59-2 DELAY
5015
59-1 PICKUP V2
5016
59-2 PICKUP V2
5017A
59-1 DOUT RATIO
5018A
59-2 DOUT RATIO
5019
59-1 PICKUP V1
5020
59-2 PICKUP V1
5101
FCT 27
5102
27-1 PICKUP
5103
27-1 PICKUP
5106
27-1 DELAY
130
Setting Options
OFF
ON
Alarm Only
20 .. 260 V
20 .. 150 V
0.00 .. 100.00 sec; ∞
20 .. 260 V
20 .. 150 V
0.00 .. 100.00 sec; ∞
2 .. 150 V
2 .. 150 V
0.90 .. 0.99
0.90 .. 0.99
20 .. 150 V
20 .. 150 V
OFF
ON
Alarm Only
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
Default Setting
Comments
OFF
59 Overvoltage Protection
110 V
59-1 Pickup
110 V
59-1 Pickup
0.50 sec
59-1 Time Delay
120 V
59-2 Pickup
120 V
59-2 Pickup
0.50 sec
59-2 Time Delay
30 V
59-1 Pickup V2
50 V
59-2 Pickup V2
0.95
59-1 Dropout Ratio
0.95
59-2 Dropout Ratio
110 V
59-1 Pickup V1
120 V
59-2 Pickup V1
OFF
27 Undervoltage Protection
75 V
27-1 Pickup
45 V
27-1 Pickup
1.50 sec
27-1 Time Delay
E50417-G1140-C343-A8, Edition 12.2017
SIPROTEC 4, 7SJ80, Manual