Siemens SIPROTEC 4 Manual page 491

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr. Parameter
5504
27/Q Direction
5511
Q> Pickup
5512
U< Pickup
5513
Delay Gen. CB
5514
Delay Grid CB
5521
Recl. release
5522
U> Reclose
5523
T Reclose
5524
Pos. f-diff
5525
Neg. f-diff
5526A Incl. 27/Q Trip
6001
S1: RE/RL
6002
S1: XE/XL
6003
S1: x'
6004
S1: x'
6005
S1: Line angle
6006
S1: Line length
6007
S1: Line length
6011
S2: RE/RL
6012
S2: XE/XL
6013
S2: x'
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Function
C
Setting Options
27/Q
Forward
Reverse
27/Q
1A
1.70 ..
10000.00 VAR
5A
8.50 ..
50000.00 VAR
27/Q
10.00 .. 210.00 V
27/Q
0.00 .. 60.00 sec
27/Q
0.00 .. 60.00 sec
27/Q
OFF
ON
27/Q
10.00 .. 210.00 V
27/Q
0.00 .. 3600.00 sec 0.00 sec
27/Q
0.01 .. 5.00 Hz
27/Q
-5.00 .. -0.01 Hz
27/Q
NO
YES
P.System Data
-0.33 .. 7.00
2
P.System Data
-0.33 .. 7.00
2
P.System Data
1A
0.0050 ..
2
15.0000 Ω/mi
5A
0.0010 ..
3.0000 Ω/mi
P.System Data
1A
0.0050 ..
2
9.5000 Ω/km
5A
0.0010 ..
1.9000 Ω/km
P.System Data
10 .. 89 °
2
P.System Data
0.1 .. 650.0 Miles
2
P.System Data
0.1 .. 1000.0 km
2
P.System Data
-0.33 .. 7.00
2
P.System Data
-0.33 .. 7.00
2
P.System Data
1A
0.0050 ..
2
15.0000 Ω/mi
5A
0.0010 ..
3.0000 Ω/mi
Functions, Settings, Information
Default Setting
Comments
Forward
Direction of 27/Q
8.70 VAR
Reactive power threshold
for pickup
43.50 VAR
85.00 V
Undervoltage threshold
for pickup
0.50 sec
Trip time delay generator
CB
1.50 sec
Trip time delay grid CB
OFF
Reclosure release
95.00 V
Voltage threshold for
reclosure rel.
Reclosure Delay Time
0.05 Hz
Pos. f-diff threshold for
reclosure rel.
-2.50 Hz
Neg. f-diff threshold for
reclosure rel.
NO
Include 27/Q Trip for
reclosure rel.
1.00
S1: Zero seq. compen-
sating factor RE/RL
1.00
S1: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S1: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S1: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S1: Line angle
62.1 Miles
S1: Line length in miles
100.0 km
S1: Line length in kilo-
meter
1.00
S2: Zero seq. compen-
sating factor RE/RL
1.00
S2: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S2: feeder reactance per
mile: x'
0.0484 Ω/mi
F.2 Settings
491