Siemens SIPROTEC 4 Manual page 473

Overcurrent time protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr. Parameter
0
VOLTAGE
0
POWER
0
VOLTAGE SYSTEM
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T PICKUP DELAY
0
T PICKUP DELAY
0A
T DROPOUT DELAY Flx
0A
BLK.by Vol.Loss
0A
DROPOUT RATIO
0A
DROPOUT RATIO
0
DO differential
201
CT Starpoint
202
Vnom PRIMARY
203
Vnom SECONDARY P.System Data
SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017
Function
C
Setting Options
Flx
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
Vx
Flx
Ia Va-n
Ib Vb-n
Ic Vc-n
Flx
Phase-Phase
Phase-Ground
Flx
0.05 .. 40.00 A
Flx
1A
0.05 .. 40.00 A
5A
0.25 .. 200.00 A
Flx
1A
0.001 .. 1.500 A
5A
0.005 .. 7.500 A
Flx
2.0 .. 260.0 V
Flx
2.0 .. 200.0 V
Flx
40.00 .. 60.00 Hz
Flx
50.00 .. 70.00 Hz
Flx
0.10 .. 20.00 Hz/s
Flx
1A
2.0 .. 10000.0 W
5A
10.0 .. 50000.0 W
Flx
1A
2.0 .. 10000.0 VAR
5A
10.0 .. 50000.0 VAR 1000.0 VAR
Flx
-0.99 .. 0.99
Flx
15 .. 100 %
Flx
4 .. 100 V/s
Flx
2.0 .. 260.0 V
Flx
0.00 .. 3600.00 sec 1.00 sec
Flx
0.00 .. 60.00 sec
Flx
0.00 ..
28800.00 sec
0.00 .. 60.00 sec
Flx
NO
YES
Flx
0.70 .. 0.99
Flx
1.01 .. 3.00
Flx
0.02 .. 1.00 Hz
P.System Data
towards Line
1
towards Busbar
P.System Data
0.10 .. 800.00 kV
1
34 .. 225 V
1
Functions, Settings, Information
Default Setting
Comments
Please select
Voltage
Ia Va-n
Power
Phase-Phase
Voltage System
2.00 A
Pickup Threshold
2.00 A
Pickup Threshold
10.00 A
0.100 A
Pickup Threshold
0.500 A
110.0 V
Pickup Threshold
110.0 V
Pickup Threshold
51.00 Hz
Pickup Threshold
61.00 Hz
Pickup Threshold
5.00 Hz/s
Pickup Threshold
200.0 W
Pickup Threshold
1000.0 W
200.0 VAR
Pickup Threshold
0.50
Pickup Threshold
20 %
Pickup Threshold
60 V/s
Pickup Threshold
110.0 V
Pickup Threshold
Trip Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Dropout Time Delay
YES
Block in case of Meas.-
Voltage Loss
0.95
Dropout Ratio
1.05
Dropout Ratio
0.03 Hz
Dropout differential
towards Line
CT Starpoint
20.00 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage
(L-L)
F.2 Settings
473