Table 128. C445 Modbus Register Map, continued
Register
Name
778
Run Interlock inputs
787
Remote Switch from
Fieldbus
900
FLA Motor1 Scaled
901
FLA Motor2 Scaled
902
Rated Service Factor
Scaled
Attribute
BYTE RW NV
Array size: 18
Default:
0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
Bitfield
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
BOOL RW NV
Default: 0
Range: 0 to 1
Config CRC
Admin Lock
USB Lock
Backup Mem
UINT16 RW NV
Default: 101
Range: 1 to 65535 (RW)
Units: scaled A
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT16 RW NV
Default: 101
Range: 1 to 65535 (RW)
Units: scaled A
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT8 RW NV
Default: 115
Range: 100 to 255
Units: 0.01%
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Appendix D—Modbus Register Map
Description
Define which inputs are run interlock inputs, If set, corresponding input
must be enabled to run motor, continued.
Bit
Description
136
ELC input x170
137
ELC input x171
138
ELC input x172
139
ELC input x173
140
ELC input x174
141
ELC input x175
142
ELC input x176
143
ELC input x177
Define Run Interlock Inputs.
Remote Switch from Fieldbus - when set to true, allows fieldbus to set
control mode to remote Remote Switch from Fieldbus.
Motor1 Overload FLA (Nominal Current) Scaled - Scaled Full Load
Amperes for the motor from the motor nameplate. If this is an application
with a 2 motor profile, this is the first motor. Scaled by parameter "I Scale
Factor".
Motor2 Overload FLA (Nominal Current) Scaled - Scaled Full Load
Amperes for the motor from the motor nameplate. If this is an application
with a 2 motor profile, this is the second motor. Scaled by parameter "I
Scale Factor".
This is the percentage of overloading the motor can handle for short
periods of time when operating normally within the correct voltage
tolerances. This value is from the motor nameplate.
Coil
12569
12570
12571
12572
12573
12574
12575
12576