Modules Overview; Figure 7. Base Control Module Image; Figure 8. Base Module Features And Connections-Front View - Eaton Power Xpert C445 User Manual

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Chapter 1—Power Xpert C445 Overview

Modules Overview

Base Control Module Basic Overview
The Base Control Module is the controller of the C445
system, providing the various monitoring, protection and
control algorithms. Equipped with native I/O connections,
communication card options and USB connectivity, the Base
Control Module provides users with real-time data on the
health and status of their applications. Various pre-configured
operation modes are available that simplify the wiring and
logic requirements for the user.

Figure 7. Base Control Module Image

Base Control Module Features
Motor protection
Current, voltage, power and system monitoring
Pre-configured operating modes
120/240 Vac or 24 Vdc supply voltage options
Four 120 Vac or 24 Vdc inputs, 2NO and 1NO/1NC relay
outputs
Integrated USB port
Real-time clock and memory backup module option slot
Multiple fieldbus communication options
Status LEDs
Provides power and communications to the Measurement
Module and the user interface through the cable
connection
6
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Figure 8. Base Module Features and Connections—
Front View
DIP Switches
Output Status
Input Status
Inputs
Test/Reset
DIP Switches: Used for node addressing and configuration
selections.
Output Status: LEDs indicate the ON/OFF status of each
output.
Input Status: LEDs indicate the ON/OFF status of each input.
Inputs: Four digital inputs available. Must be purchased as
24 Vdc or 120 Vac.
Test/Reset: Used to manually trip the Base Control Module.
Also used to reset the module after a trip has occurred.
USB Port: Micro AB connector. Enables configuration upload.
Status LEDs:
Status: Indicates the fault and warning status of the Base
Control Module
CH1: Indicates status of modules attached to Channel 1
port on Base Control Module (Measurement Module or
user interface)
CH2: Indicates status of modules attached to Channel 2
port on Base Control Module (Measurement Module or
user interface)
USB: USB traffic indication
Real Time Clock and Memory Backup Module: Optional real
time clock module. Plugs in behind the communication
cards. Provides battery backed-up fault time stamping and
non-volatile memory for configuration parameters.
Communication Cards: Optional modules to provide
communications.
PROFIBUS DVP0 and DVP1 (Shown)
Ethernet for Modbus/TCP and EtherNet/IP
Communication
Modules
RTC Module
Status LEDs
USB Port

Advertisement

Table of Contents
loading

Table of Contents