Eaton Power Xpert C445 User Manual page 53

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

30: Warning Status Bits – PTC
31: Warning Status Bits – Phase Rotation
32: Warning Status Bits – Stall
33: Warning Status Bits – Overload
34: Warning Status Bits - exceeds starts limit
35: Warning Status Bits – Low Power
36: Warning Status Bits – High Power
37: Warning Status Bits – Under Current
38: Warning Status Bits – Frequency Deviation Slow
39: Warning Status Bits – Frequency Deviation Fast
40: Warning Status Bits – Voltage Unbalance
41: Warning Status Bits – Voltage Phase Loss
42: Warning Status Bits – PF Deviation
43: Warning Status Bits – Jam
44: Warning Status Bits – Instantaneous Over Current
45: Warning Status Bits – Current Unbalance
46: Warning Status Bits – Current Phase Loss
47: Warning Status Bits – Residual GF
48: Warning Status Bits – External GF
49: Warning Status Bits – Overvoltage
50: Warning Status Bits – Undervoltage
51: Tripped Status Bits – Undervoltage
52: Tripped Status Bits – Overvoltage
53: Tripped Status Bits – External GF
54: Field Output Control word – bit 0
55: Field Output Control word – bit 1
56: Field Output Control word – bit 2
57: Field Output Control word – bit 3
58: Shunt Trip Output
59: Warning Status Bits – HRGF Pulse Detect
60: Warning Status Bits – Peak Demand
61: Base Control Module Field Input I1
62: Base Control Module Field Input I2
63: Base Control Module Field Input I3
64: Base Control Module Field Input I4
65: Tripped Status Bits (Fail Safe) – Not Ground Current
Outputs 1 and 2 are normally open form A relay outputs.
Output 3 is a form C relay output with one normally open and
one normally closed contact. When the output is energized,
both contacts change state. When ordering the C445 Motor
Management Relay, one of the options is to obtain a Base
Control Module where Output 3 is either a standard form C
relay output or a latching form C relay output.
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Chapter 3—Installation and Wiring
Output 3 operation as a standard form C relay output means
the output will de-energize and return the contacts to their
normal state when the Base Control Module is powered off.
Output 3 operation as a latching relay output offers capability
beyond what's available from a non-latching, or a standard
relay output. The energized state of the latching relay can be
maintained after power has been removed from the Base
Control Module. Energized means that the normally open
contact will be closed and the normally closed contact
will be open.
There are two additional configuration parameter for the
latching relay and that involves the Power-down behavior.
The following are the four choices for this behavior. These
parameter can be configured using the Power Xpert
inControl Software or via a Modbus message from a Modbus
master. These parameters are called:
Base Control Module Relay 3 Behavior (Modbus register 719):
Behave like a non-latching relay (default) (Modbus value = 0)
Behave like a latching relay (Modbus value = 1)
If "Behave like a latching relay" is selected for the parameter
above, then the following options are available in the
Output 3 Latching Relay Behavior at Power Down parameter
(Modbus register 729):
Turn Off (default) (Modbus value = 0)
Turn On (Modbus value = 1
Hold Last State (Modbus value = 2)
Toggle (Modbus value = 3)
The four bits in the Base Control Module Field Output
Control word (Modbus register 601) can be assigned in any
order to control the various outputs as follows:
Output 1 Function Select: Select Field Output Control
Word bit 0, 1, 2 or 3
Output 2 Function Select: Select Field Output Control
Word bit 0, 1, 2 or 3
Output 3 Function Select: Select Field Output Control
Word bit 0, 1, 2 or 3
Output 3 Reset Function Select: Select Field Output
Control Word bit 0, 1, 2 or 3 (for Latching Relay
Operation only)
Refer to Appendix E for a complete C445 Modbus
register map.