Direct Operation Mode
Description
Direct Motor starter is the default profile. The Direct Motor
starter profile will use the motor1 parameters for all control/
protections.
C445 outputs:
Output 1 is dedicated by this application mode for
●
controlling and protecting the motor
Outputs 2 and 3 are general purpose
●
Output 1 controls and protects the contactor/motor. It will
close when a valid RUN command is received by the C445,
provided a fault or inhibit is not active and will open on a
STOP command or if a trip occurs. A C445 Trip condition will
cause the Output contact to open.
Outputs 2 and 3 are user configurable outputs and their
function can be selected by the user.
The C445 will issue a control fault when:
Run command is active and phase voltage is present
●
with no phase current detected after delay expires
Stop command active and current detected after
●
delay expires
Figure 63. Timing Diagram for the Direct Mode Operation
Timing Diagram
Control Fault delay
RUN
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Chapter 5—System Configuration and Operation
Recommended User Interface Options for the
Direct Operation Mode
Figure 64. C445UM: Monitoring User Interface
The Monitoring User Interface can be used with any
operation mode. If selected as a local control source, the
User Interface Start and Stop buttons are enabled in Direct
Mode. Users may optionally disable local start or reset
functionality if desired.
C445UM may still be used in Direct Mode if the User
Interface is not the local control source. Start, Stop and Auto
buttons will be disabled. If pressed, the screen will notify the
user that this functionality is not enabled. Control Status
LEDs indicating running, stopped and Auto status will still
function.