Advertisement

Chapter 6—Motor Protection
Current Phase Loss
The Current Phase Loss protection monitors the current
unbalance of the motor and will trip the motor if the
unbalance exceeds the set threshold. The Current Phase
Loss protection is active when the motor is in the Running
state.
If a C445 relay is commissioned to monitor an AC motor, the
current must be fed on all three poles to prevent early
tripping.
Measurement Precondition Imax>50% of FLA, Imin<25% of
FLA, No V Phase Loss (or no voltage option)
Measurement Parameter Current unbalance percent

Table 38. Current Phase Loss

Fault
Code
Protection
Action
5
Current Phase Loss Fault Trip
Undercurrent
Undercurrent Trip Level protection monitors the three phase
currents and will fault if the measured current drops below
the set threshold.

Table 39. Undercurrent

Fault
Code
Protection
Action
14
Undercurrent
Fault Trip
Fault Warning
132
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Fault Action
Modbus
Units
Min.
1016
%
60
Fault Action
Modbus
Units
Min.
1021
% FLA
10
1022
% FLA
10
Delay (Seconds)
Max.
Default
Min.
60
60
2
Delay (Seconds)
Max.
Default
Min.
90
50
1
90
50
0.2
Max.
Default
Modbus
2
2
1017
Max.
Default
Modbus
60
20
1023
5
2
1079