Table 33. Overload; Table 34. Instantaneous Overcurrent - Eaton Power Xpert C445 User Manual

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Chapter 6—Motor Protection
Motor Thermal Overload
The Overload function models the thermal characteristics of
a motor and generates a Fault Trip event that de-energizes
the motor before motor damage will occur. This is intended
to protect the motor and power wiring from excessive
current. Trip curves are defined by applicable agency
standards. The trip class for any particular Overload class is
user adjustable.

Table 33. Overload

Fault
Code
Protection
Action
19
Thermal Overload
Fault Trip
Fault Warning
Overload Reset
Threshold
Instantaneous Overcurrent
The Instantaneous Overcurrent protection monitors the
maximum phase current of the motor and will trip the motor
if the current exceeds the set threshold. The Instantaneous
Current protection is active when the motor is energized but
does have a separate Start delay to account for high starting
currents that are characteristic of high efficiency induction
motors.

Table 34. Instantaneous Overcurrent

Fault
Code
Protection
Action
7
Instantaneous
Fault Trip
Overcurrent
Fault Warning
Fault Trip Delay
130
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Fault Action
Default
Status
Units
Note
Enabled
amps
C445MA2P2... 0.3
C445MA005... 1
C445MA032... 4
C445MA045... 6
C445MB072... 9
C445MC090... 11
C445MC136... 17
C445...ext
Disabled
%
%
C445...
Fault Action Settings
Modbus
Units
Min.
1012
% FLA
50
1013
% FLA
50
At powerup
Min.
Max.
Default
2.4
0.3
5
1
32
4
45
6
72
9
90
11
136
17
ext
800
ext
1
100
90
1
99
75
Delay (Seconds)
Max.
Default
Min.
400
400
1
400
400
200
0
Delay (Seconds)
Min.
Max.
Default
Class 5
Class 40
Class 5
Class 5
Class 40
Class 5
Class 5
Class 40
Class 5
Class 5
Class 40
Class 5
Class 5
Class 40
Class 5
Class 5
Class 40
Class 5
Class 5
Class 40
Class 5
Class 5
Class 40
Class 5
Max.
Default
Modbus
2000
2000
1015
5000
2000
1079
18000
0
1014